| Code | Description | Quantity | Note |
|---|---|---|---|
| Basic | Required for basic functionality | ||
| 01_bm-gw | BTMS IOT Gateway | 1 × BM-GW for up to 32 strings | All strings of one UPS should be on the same BM-GW |
| 02_bm-ss | BTMS String master | 1 × BM-SS for each string | |
| 03_bm-hs | BTMS Hall sensor | 1 × BM-HS for each string | Choose the type based on the maximum string current |
| 04_bm-cs | BTMS Cell sensor | 1 × BM-CS for each battery | Choose 2, 6 or 12 V sensors depending on the battery voltage |
| 05_bm-ps | BTMS Power supply | 1 × PS-60-24 for each BTMS | One power supply can power several devices, if there are fewer of them than allowed according to thespecification. Checks against the total consumption of powered devices. |
| 05_ps-30-12 | BM-GW Power supply | 1 × PS-30-12 for each BM-GW | |
| Optional | Depending on requirements | ||
| 06_bm-mc | BTMS Master controller | 1 × BM-MC for up to 32 strings | |
| 06_bm-c-A1 | BTMS Controller set | 1 × BM-C-A1 for up to 32 strings | Consisting of 06_bm-mc, 07_bm-cad and software |
| 07_bm-cad | BTMS COM converter | 1 × BM-CAD per BM-HMI | They require BM-MC |
| 07_bm-com | BTMS COM module | 1 × BM-COM for up to 16 BM-CS | For more than 16 BM-CS (up to 32) use 2nd BM-COM |
| 07_bm-lc | BTMS IO expansion module | 1 × BM-LC for up to 8 strings | They require BM-MC |
| 08_bm-th | BTMS Temperature and humidity sensor | 1 × BM-TH for every string | They require BM-MC |
| 08_bm-gs | BTMS Insulation monitoring sensor | 1 × BM-GS for every string | They require BM-MC and BM-COM |
| 09_bm-hmi | BTMS Human-Machine Interfaces | 1 × BM-HMI for up to 32 strings | They require BM-C-A1 (BM-MC + BM-CAD), 1 per BM-C-A1 |
| 10_bm-ag | BTMS IOT Aggregator | 1 × BM-AG per Data center | Needed when there are multiple BM-GWs on the Data Center |
| 06_th-mc | Temperature and humidity monitoring Master controller | 1 × TH-MC for up to 120 temperature-humidity sensors | |
| 06_tm-c-A1 | Temperature and humidity monitoring Controller set | 1 × TH-MC for up to 120 temperature-humidity sensors | Consisting of 06_th-mc, 07_bm-cad and software |
System limitations
| Device | Supports up to |
|---|---|
| BM-AG | unlimited BM-GW |
| BM-GW | 32 × BM-SS, 1 × BM-MC |
| BM-MC | 32 × BM-TH, 4 × BM-LC, 1 × BM-HMI |
| BM-SS | 120 × BM-CS |
===== Standard cabinets ===== 07_bm-cad