User Tools

Site Tools


hiq:components:air-12

AiR-12

Resistive inputs (RTD) 12xPt100/1000, Ni100/1000 or potentiometer

air-12_main_picture.jpg

Model number: AiR-12
Mounting: DIN rail

Features

  • IEX-2 module
  • 12 RTD inputs

Technical specification

Input type Pt100/1000 (DIN751) auto selectable, measuring range -100..300°C
Ni100/1000 (DIN43760) auto selectable, measuring range -50..160°C
Ni100/1000 (Landis & Gyr) auto selectable, measuring range -50..160°C
potentiometer 0..2000ohm
Sensor current 190uA (each sensor)
Wire resistance 20ohm max. (3-wire mode)
Resolution 14 bits in 0.1% mode
12 bits in 0.5% and 1% mode
Temperature drift +/-0.01%/°C of measuring range
Scan time 30ms..980ms, depends on input mode
Calibration reference 150.00ohm, 1500.0ohm
Power supply 24V (18..28V), 50mA
Galvanic isolation 1kV between digital and analog circuit
no isolation between chanels
Operating conditions 0..50°C, 0..85% rh non-condensing
Weight 160g
Degree of protection IP20
Level of ambient pollution 2
Standards EN 61010-1, EN 61010-2-201, EN 61131-2

Terminals

Dimensions

hiq/components/air-12.txt · Last modified: 2023/12/18 13:32 by alen.mejak