Resistive inputs (RTD) 12xPt100/1000, Ni100/1000 or potentiometer
Model number: | AiR-12 |
---|---|
Mounting: | DIN rail |
Features
- IEX-2 module
- 12 RTD inputs
Technical specification
Input type | Pt100/1000 (DIN751) auto selectable, measuring range -100..300°C |
Ni100/1000 (DIN43760) auto selectable, measuring range -50..160°C | |
Ni100/1000 (Landis & Gyr) auto selectable, measuring range -50..160°C | |
potentiometer 0..2000ohm | |
Sensor current | 190uA (each sensor) |
Wire resistance | 20ohm max. (3-wire mode) |
Resolution | 14 bits in 0.1% mode |
12 bits in 0.5% and 1% mode | |
Temperature drift | +/-0.01%/°C of measuring range |
Scan time | 30ms..980ms, depends on input mode |
Calibration reference | 150.00ohm, 1500.0ohm |
Power supply | 24V (18..28V), 50mA |
Galvanic isolation | 1kV between digital and analog circuit |
no isolation between chanels | |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
Weight | 160g |
Degree of protection | IP20 |
Level of ambient pollution | 2 |
Standards | EN 61010-1, EN 61010-2-201, EN 61131-2 |