 Procedure to activate Dynamic Load Management is as follows: Procedure to activate Dynamic Load Management is as follows:
   * [[wiki:20_rdc_charger:30_software:start#hems_configurator|HEMS Configurator]] -> settings -> Virtual grid PS must be disabled (1)   * [[wiki:20_rdc_charger:30_software:start#hems_configurator|HEMS Configurator]] -> settings -> Virtual grid PS must be disabled (1)
-  * Wire [[wiki:20_rdc_charger:15_hardware:20_pm1|PM1-E-D]] or [[wiki:20_rdc_charger:15_hardware:21_pm3|PM3-E-D]] to [[wiki:20_rdc_charger:25_wiring:start#wireless_power_sensors_wiring|WM-1]] module (set address to 150 or use default address 149)+  * Wire [[wiki:20_rdc_charger:15_hardware:20_pm1|PM1-E-D]] or [[wiki:20_rdc_charger:15_hardware:21_pm3|PM3-E-D]] to [[wiki:20_rdc_charger:25_wiring:start#wireless_power_sensors_wiring|WM-1]] module (use default address 149 or manually set address to 150)
   * HEMS Configurator -> settings -> select WM/WR pairing button and follow [[wiki:20_rdc_charger:35_commissioning:03_wr_wm|WM/WR pairing instructions]] (2) (3)   * HEMS Configurator -> settings -> select WM/WR pairing button and follow [[wiki:20_rdc_charger:35_commissioning:03_wr_wm|WM/WR pairing instructions]] (2) (3)
 {{wiki:20_rdc_charger:hems_config_dynamic_01.png?direct&800|}} {{wiki:20_rdc_charger:hems_config_dynamic_01.png?direct&800|}}