General description
V3.1 - GRMS Room Compact Wireless - MC-230-01 + EnOcean is a compact GRMS room variant based on the MC-230-01 controller with integrated RS485 communication and EnOcean wireless sensor option.
This variant is intended for rooms where reduced cabling is required, especially for retrofit or renovation projects where window sensor wiring is difficult or not preferred.
Typical use
This variant is suitable for rooms requiring:
- compact controller configuration
- integrated RS485 / Modbus communication
- direct IEX connection
- EnOcean wireless sensor integration
- reduced cabling for window contact or selected room sensors
- simplified retrofit installation
- Ethernet / Linker connection to S-RMS
Main components
| Group | Component code | Description |
|---|---|---|
| Room controller | MC-230-01 | Main room controller with integrated Ethernet, RS485, IEX-2 terminals and EnOcean gateway. |
| Power supply | 230 VAC / MC-230-01 supply | Controller supply. Only one supply option is used according to project configuration. |
| IEX connection | MC-230-01 IEX-2 terminals | Direct IEX device connection without CAD-BC module. |
| RS485 / Modbus | MC-230-01 RS485 | Integrated RS485 communication for Modbus fan-coil, recuperator or compatible HVAC equipment. |
| EnOcean window sensor | SWO-2-1-00 | EnOcean wireless invisible battery-free opening sensor for HVAC interlock without additional cabling to the window. |
| Corridor access panel | CR-D1-V2-PX-BK | Corridor-side access panel for room access, door status and lock control. |
| Door lock | EL-B / EL-N | Electric door strike, selected according to door type and installation requirements. |
| Room touch panel assembly | TGP-4D-01-IQ + TGP-S | In-room 4 inch touch HMI panel with TGP-S adapter/interface board for connecting the ES-W2 room temperature sensor. |
| Room temperature sensor | ES-W2-WH / ES-W2-BK | Room temperature sensor connected through TGP-S and used for HVAC regulation. |
| Room PIR sensor | IR-R-IW-WH / IR-R-OW-WH | Presence / motion sensor for occupancy and energy-saving logic. |
| HVAC outputs | MC-230-01 outputs / RS485 | HVAC control through local outputs or RS485 communication, depending on equipment. |
| Network | Ethernet / Linker | Connection to S-RMS. |
Connected room functions
| Function | Connected elements |
|---|---|
| Access control | CR-D1-V2-PX-BK, EL-B / EL-N and door status. |
| Guest interface | TGP-4D-01-IQ room touch panel with TGP-S adapter and room commands. |
| Room temperature | ES-W2-WH / ES-W2-BK connected through TGP-S. |
| HVAC | RS485 / Modbus HVAC device or local HVAC outputs, depending on equipment. |
| Wireless sensing | SWO-2-1-00 EnOcean wireless opening sensor for HVAC interlock. |
| Room sensing | ES-W2 room temperature sensor and PIR sensor. |
| Energy saving | Presence detection, window status, managed power supply and HVAC interlock logic. |
| Central system | Ethernet connection to Linker and S-RMS. |
Variant difference
Compared to V3 - GRMS Room Compact Modbus - MC-230-01, this variant adds SWO-2-1-00 EnOcean wireless opening sensor integration, typically for a wireless window contact.
Notes
- V3.1 is recommended for retrofit rooms where wiring to the window is difficult.
- TGP-S is part of the room touch panel assembly and is used as the interface board for connecting the ES-W2 room temperature sensor.
- EnOcean device compatibility and radio coverage must be checked per project.
- Final HVAC and sensor configuration depends on the selected equipment and room layout.