V1 - GRMS Room Base - MC-24-H1

General description

V1 - GRMS Room Base - MC-24-H1 is the base standard GRMS room variant for a full hotel room automation system based on the MC-24-H1 hotel room controller.

This configuration is intended for standard hotel rooms where the GRMS system manages access control, guest room control, HVAC, lighting, blinds, room presence, window status, energy-saving logic and communication with the central S-RMS system through Linker.

V1 is the reference configuration for other MC-24-H1 based room variants.

Typical use

This variant is suitable for rooms requiring a complete standard GRMS setup with:

  • corridor access panel
  • door lock and door status
  • in-room touch panel with TGP-S adapter
  • ES-W2 room temperature sensor
  • fan-coil regulation through FC-1-IQ
  • standard lighting circuits
  • one blind group
  • presence detection
  • window contact monitoring
  • SOS input
  • master off function
  • floor heating and ventilation output
  • energy-saving logic
  • Ethernet / Linker connection to S-RMS

Main components

Group Component code Description
Room controller MC-24-H1 Main hotel room controller for local room automation, I/O handling and Ethernet communication.
Power supply HDR-30-24 24 VDC power supply for controller and bus devices.
Bus interface CAD-BC Bus coupler used to connect MC-24-H1 to IEX bus devices.
Corridor access panel CR-D1-V2-PX-BK Corridor-side access panel for room access, door status and lock control.
Door lock EL-B / EL-N Electric door strike, selected according to door type and installation requirements.
Room touch panel assembly TGP-4D-01-IQ + TGP-S In-room 4 inch touch HMI panel with TGP-S adapter/interface board for connecting the ES-W2 room temperature sensor.
Room temperature sensor ES-W2-WH / ES-W2-BK Room temperature sensor connected through TGP-S and used for HVAC regulation and room comfort control.
Fan-coil module FC-1-IQ 3-speed fan coil actuator for fan and valve control.
Room PIR sensor IR-R-IW-WH / IR-R-OW-WH Presence / motion sensor for occupancy and energy-saving logic.
Window contact MOS-03-HD-WH / MOS-04-VS-WH / MOS-04-VS-BK Wired magnetic opening sensor for window status and HVAC interlock.
Network Ethernet / Linker Connection to S-RMS.

Connected room functions

Function Connected elements
Access control CR-D1-V2-PX-BK, EL-B / EL-N, door reed sensor, RFID / QR / PIN depending on panel configuration.
Guest interface TGP-4D-01-IQ room touch panel with TGP-S adapter and room commands.
Room temperature ES-W2-WH / ES-W2-BK connected through TGP-S.
HVAC FC-1-IQ, fan-coil valves, 3-speed fan, ES-W2 room temperature sensor and window interlock.
Lighting Standard room lighting circuits, including welcome light.
Blinds One motorized blind group with up/down control.
Energy saving IR-R-IW-WH / IR-R-OW-WH, window contact, managed power supply and master off function.
Safety / alarm SOS input and room status reporting.
Central system Ethernet connection to Linker and S-RMS.

Notes

  • V1 is the base standard full-room configuration.
  • It should be used as the reference for standard MC-24-H1 based GRMS rooms.
  • TGP-S is part of the room touch panel assembly and is used as the interface board for connecting the ES-W2 room temperature sensor.
  • Detailed I/O allocation is defined in the electrical scheme and technical documentation.
standard_room_variants/v1_grms_room_base_mc24_h1.txt · Last modified: by paulo.krbavcic