V1.3 - GRMS Room Full Option - MC-24-H1 + LC-10-IQ-MK2 + CAD-232-A3-IQ

General description

V1.3 - GRMS Room Full Option - MC-24-H1 + LC-10-IQ-MK2 + CAD-232-A3-IQ is the most extended MC-24-H1 based standard room variant.

It combines the full V1 room configuration with an additional LC-10-IQ-MK2 module for expanded lighting and blinds control, and CAD-232-A3-IQ for RS485 / Modbus communication.

Typical use

This variant is suitable for larger or more complex rooms requiring:

  • all standard V1 room functions
  • additional lighting circuits
  • additional blind groups
  • RS485 / Modbus communication
  • connection to a recuperator or compatible HVAC device
  • extended room scene and control options
  • Ethernet / Linker connection to S-RMS

Main components

Group Component code Description
Room controller MC-24-H1 Main hotel room controller for local room automation and Ethernet communication.
Power supply HDR-30-24 24 VDC power supply for controller and bus devices.
Bus interface CAD-BC Bus coupler used to connect MC-24-H1 to IEX bus devices.
Light control extension LC-10-IQ-MK2 10 high power relay-controlled outputs for additional lighting and blinds control.
RS485 module CAD-232-A3-IQ A-bus RS232 to RS485 converter used for RS485 / Modbus communication.
Corridor access panel CR-D1-V2-PX-BK Corridor-side access panel for room access, door status and lock control.
Door lock EL-B / EL-N Electric door strike, selected according to door type and installation requirements.
Room touch panel assembly TGP-4D-01-IQ + TGP-S In-room 4 inch touch HMI panel with TGP-S adapter/interface board for connecting the ES-W2 room temperature sensor.
Room temperature sensor ES-W2-WH / ES-W2-BK Room temperature sensor connected through TGP-S and used for HVAC regulation.
Fan-coil module FC-1-IQ 3-speed fan coil actuator for fan and valve control.
Room PIR sensor IR-R-IW-WH / IR-R-OW-WH Presence / motion sensor for occupancy and energy-saving logic.
Window contact MOS-03-HD-WH / MOS-04-VS-WH / MOS-04-VS-BK Wired magnetic opening sensor for window status and HVAC interlock.
Network Ethernet / Linker Connection to S-RMS.

Connected room functions

Function Connected elements
Access control CR-D1-V2-PX-BK, EL-B / EL-N and door status.
Guest interface TGP-4D-01-IQ room touch panel with TGP-S adapter and room commands.
Room temperature ES-W2-WH / ES-W2-BK connected through TGP-S.
HVAC FC-1-IQ, fan-coil valves, 3-speed fan, ES-W2 room temperature sensor and window interlock.
RS485 / Modbus Recuperator or compatible HVAC device through CAD-232-A3-IQ.
Lighting Base lighting circuits and additional LC-10-IQ-MK2 controlled lighting circuits.
Blinds Base blind group and additional blind groups through LC-10-IQ-MK2.
Energy saving PIR sensor, window contact, managed power supply and master off function.
Central system Ethernet connection to Linker and S-RMS.

Variant difference

Compared to V1 - GRMS Room Base - MC-24-H1, this variant adds both:

  • LC-10-IQ-MK2 for additional lighting and blinds
  • CAD-232-A3-IQ for RS485 / Modbus communication

Notes

  • V1.3 is recommended for the most equipped MC-24-H1 based rooms.
  • TGP-S is part of the room touch panel assembly and is used as the interface board for connecting the ES-W2 room temperature sensor.
  • It is suitable where both extended room I/O and communication with external HVAC equipment are required.
  • Detailed I/O and Modbus allocation are defined in the project electrical scheme.