V1.2 - GRMS Room Base Modbus - MC-24-H1 + CAD-232-A3-IQ

General description

V1.2 - GRMS Room Base Modbus - MC-24-H1 + CAD-232-A3-IQ is a standard full GRMS room variant based on the MC-24-H1 controller with an additional CAD-232-A3-IQ communication module.

This variant is intended for rooms where RS485 / Modbus communication is required, typically for a recuperator, Modbus HVAC device or similar external technical equipment.

Typical use

This variant is suitable for rooms requiring:

  • all standard V1 room functions
  • RS485 / Modbus communication
  • connection to a recuperator
  • communication with compatible HVAC equipment
  • central supervision of communication-based equipment where supported
  • Ethernet / Linker connection to S-RMS

Main components

Group Component code Description
Room controller MC-24-H1 Main hotel room controller for local room automation and Ethernet communication.
Power supply HDR-30-24 24 VDC power supply for controller and bus devices.
Bus interface CAD-BC Bus coupler used to connect MC-24-H1 to IEX bus devices.
RS485 module CAD-232-A3-IQ A-bus RS232 to RS485 converter used for RS485 / Modbus communication.
Corridor access panel CR-D1-V2-PX-BK Corridor-side access panel for room access, door status and lock control.
Door lock EL-B / EL-N Electric door strike, selected according to door type and installation requirements.
Room touch panel assembly TGP-4D-01-IQ + TGP-S In-room 4 inch touch HMI panel with TGP-S adapter/interface board for connecting the ES-W2 room temperature sensor.
Room temperature sensor ES-W2-WH / ES-W2-BK Room temperature sensor connected through TGP-S and used for HVAC regulation.
Fan-coil module FC-1-IQ 3-speed fan coil actuator for fan and valve control.
Room PIR sensor IR-R-IW-WH / IR-R-OW-WH Presence / motion sensor for occupancy and energy-saving logic.
Window contact MOS-03-HD-WH / MOS-04-VS-WH / MOS-04-VS-BK Wired magnetic opening sensor for window status and HVAC interlock.
Network Ethernet / Linker Connection to S-RMS.

Connected room functions

Function Connected elements
Access control CR-D1-V2-PX-BK, EL-B / EL-N and door status.
Guest interface TGP-4D-01-IQ room touch panel with TGP-S adapter and room commands.
Room temperature ES-W2-WH / ES-W2-BK connected through TGP-S.
HVAC FC-1-IQ, fan-coil valves, 3-speed fan and ES-W2 room temperature control.
RS485 / Modbus Recuperator or compatible HVAC device through CAD-232-A3-IQ.
Lighting Standard room lighting circuits.
Blinds One motorized blind group.
Energy saving PIR sensor, window contact, managed power supply and master off function.
Central system Ethernet connection to Linker and S-RMS.

Variant difference

Compared to V1 - GRMS Room Base - MC-24-H1, this variant adds CAD-232-A3-IQ for RS485 / Modbus communication.

Notes

  • V1.2 is recommended when the room requires communication with a recuperator or other RS485 / Modbus device.
  • TGP-S is part of the room touch panel assembly and is used as the interface board for connecting the ES-W2 room temperature sensor.
  • Final Modbus mapping depends on the connected equipment.
  • Detailed communication parameters are defined per project.