hiq_components:pm1-e-d
Table of Contents
PM1-E-D
Single phase power-sensor
Model number: | PM1-E-D |
---|---|
RS485 power sensor bus A - B | |
Mounting: | DIN rail, 1M |
Used for measuring power and energy of | |
---|---|
✔ | single-phase energy sources |
✔ | single-phase energy consumers |
Applications
- Digital multi-function power-sensor for single phase networks
Features
- DIN rail mounting with direct connection up to 45A
- Compact design in a single module 18mm wide
- Seal-able cover(phase and neutral terminals)
General description
The PM1-E-D series is an advanced single phase energy monitoring solution with built-in configuration push button and LCD data display. Particularly indicated for metering active energy and other power parameters. Housing for DIN-rail mounting, IP51 protection degree, direct connection up to max 45A.
Technical specifications
Energy Measurements | |
---|---|
Imported/Exported active energy | 0 to 99999.99 kWh |
Imported/Exported reactive energy | 0 to 99999.99 kVArh |
Total active energy | 0 to 99999.99 kWh |
Total reactive energy | 0 to 99999.99 kVArh |
Measured Inputs | |
Nominal Voltage Input | (Ph+N) 176 to 276V |
Max Continuous Voltage | 120% of nominal |
Nominal Input Current | 5(45)A |
Max Continuous Current | 120% of nominal |
Frequency | 50Hz (±10%) |
Accuracy | |
Voltage | 0·5% of range maximum |
Current | 0·5% of nominal |
Frequency | 0·2% of mid-frequency |
Power factor | 1% of unity (0.01) |
Active power (W) | ±1% of range maximum |
Reactive power (VAr) | ±1% of range maximum |
Apparent power (VA) | ±1% of range maximum |
Active energy (Wh) | Class 1 IEC 62053-21 |
Reactive energy (VARh) | ±1% of range maximum |
Modbus (RS485 Output for Modbus RTU & Pulsed Output) | |
Baud rate | 1200, 2400, 4800, 9600. |
Parity | none / odd / even |
Stop bits | 1 or 2 |
RS485 network address | 1 to 247 |
Reference Conditions of Influence Quantities | |
Ambient temperature | 23°C ±1°C |
Input waveform | 50 or 60Hz ±2% |
Input waveform | Sinusoidal (distortion factor < 0·005) |
Auxiliary supply voltage | Nominal ±1% |
Auxiliary supply frequency | Nominal ±1% |
Auxiliary supply waveform (if AC) | Sinusoidal (distortion factor < 0·05) |
Magnetic field of external origin | Terrestrial flux |
Environment | |
Operating temperature | -25°C to +55°C |
Storage temperature | -40°C to +70°C |
Relative humidity | 0 to 95%, non-condensing |
Altitude | Up to 3000m |
Warm up time | 1 minute |
Vibration | 10Hz to 50Hz, IEC 60068-2-6, 2g |
Shock | 30g in 3 planes |
Mechanics | |
DIN rail dimensions | 18mm x 90mm (WxH) per DIN 43880 |
Mounting | DIN rail (DIN 43880) |
Terminals
Dimensions
Download
hiq_components/pm1-e-d.txt · Last modified: 2023/12/13 07:10 by alen.mejak