hiq:components:mc-230-05
Table of Contents
MC-24-05
Advanced Controller
Model number: | MC-24-05 | |
---|---|---|
Description: | 24 VDC, 26 IO, 2x RS232 | |
Mounting: | DIN rail(35mm), 6M, 106mm |
Features
- 12 digital inputs
- 10 relay outputs 8 A
- 4 universal inputs/outputs
- Ethernet, USB, IEX-2, 2×RS232
- Enocean gateway (Optional → order code: MC-24-06)
- 24 VDC power supply
Safety standards
EN 61010-1, EN 61010-2-201, EN 61131-2
Technical specification
System clock | 100MHz |
Instruction execution | 10ns per instruction |
Program memory | 896Kb for user program |
Data memory | 64Kb for user variables |
Data retention | 7 days |
RTC accuracy | typ. ±2 sec per day at 25°C |
Digital input (ix00..ix11) | 24V 7mA, opto isolated, bidirectional |
Digital input (ix12..ix15) | dry contact, internal pull-up 12V 3mA |
Digital output (qx00..qx09) | relay 8A/250VAC or 8A/30VDC resistive |
Digital output (qx12..qx15) | NPN transistor 30V 1A |
IEX-2 bus load | 48 modules (Cybro + 47 IEX-2) |
IEX-2 baud rate | 20, 50, 100 (default), 250, 500kbps |
IEX-2 cable length, 100kbps | 100m (non-terminated) |
IEX-2 cable length, 100kbps | 300m (terminated) |
IEX-2 cable length, 50kbps | 500m (terminated) |
Power supply | 24V (18..28V) |
Power consumption | 50mA (no load), 180mA (10 relays, 4x 10Vout) |
Power output (IEX-2) | 24V 2A (limited by resettable fuse) |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
Degree of protection | IP20 |
Installation category | III |
Terminals
Dimensions
hiq/components/mc-230-05.txt · Last modified: 2023/12/18 13:16 by alen.mejak