hiq:components:mc-230-04
Table of Contents
MC-230-04
Advanced Controller
| Order code: | MC-230-04 | |
|---|---|---|
| Description: | 230 VAC, 11 IO, 2 × RS232 isolated, RS485, IEX2 terminals, | |
| Mounting: | DIN rail (35mm), 6M, 106mm | |
Features
- 3 digital inputs
- 4 relay outputs 8 A
- 4 universal inputs/outputs
- Ethernet, USB, IEX-2, 2×RS232, 1×RS485 isolated
- 230 VAC power supply
Safety standards
EN 61010-1, EN 61010-2-201, EN 61131-2
Technical specification
| Relay outputs: | 8A/250VAC resistive, 8A/30VDC resistive |
| Communication: | Ethernet, 2x RS232, 1x RS485, IEX-2 bus |
| Nominal power rating: | 230 VAC or 24 VDC |
| Power consumption: | typ. 1W (no load), 10W max |
| Power output: | 24V 200mA (with 230 VAC power supply) |
| Ingress protection: | IP20 |
| Operating temperature: | 0..50°C |
| Storage temperature: | -20..75°C |
| Relative humidity: | 0..85% n/c |
| Input type(ix00..ix02): | dry contact, internal pull-up 12V 2mA |
| Cable lenght: | 50m |
| COM1 type | RS485 two wire |
| Transmit/receive | automatic switching |
| MAX recommended output power per relay: | |
| - incandescent / halogen 230V | 800 W |
| - halogen 12 V with transformer | 400 W |
| - fluorescent with electronic ballast | 400 W |
| - parallel compensated fluo lamps | 250 W / 30 uF |
| - electric heater | 1400 W |
| Total output power (all relays): | 4000 W |
Terminals
Dimensions
hiq/components/mc-230-04.txt · Last modified: by alen.mejak