hiq:components:bio-8r4
Table of Contents
Bio-8R4
Features
- IEX-2 module
- 4 opto-coupler inputs 230V
- 8 relay outputs 16A with mains sense
Technical specification
Input type | 230VAC 1mA, opto isolated |
Output type | relay 16A/250VAC resistive |
Contact type | normally open |
Continuous load | 15A per relay |
75A for all relays together | |
Power supply | 24V (18..28V), 160mA |
(20mA+17mA*number of active relays) | |
Galvanic isolation | 5kV between inputs and internal circuit |
5kV between internal circuit and relay contacts | |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
36A all relays | |
Power supply | 24V (18..28V), 260mA |
(20mA+11mA*active outputs+9mA*active inputs) | |
Weight | 360g |
Degree of protection | IP20 |
Level of ambient pollution | 2 |
Standards | EN 61010-1, EN 61010-2-201, EN 61131-2 |
Terminals
Dimensions
hiq/components/bio-8r4.txt · Last modified: 2023/12/18 13:31 by alen.mejak