hiq:components:bio-8r4
Table of Contents
Bio-8R4
Features
- IEX-2 module
- 4 opto-coupler inputs 230V
- 8 relay outputs 16A with mains sense
Technical specification
| Input type | 230VAC 1mA, opto isolated |
| Output type | relay 16A/250VAC resistive |
| Contact type | normally open |
| Continuous load | 15A per relay |
| 75A for all relays together | |
| Power supply | 24V (18..28V), 160mA |
| (20mA+17mA*number of active relays) | |
| Galvanic isolation | 5kV between inputs and internal circuit |
| 5kV between internal circuit and relay contacts | |
| Operating conditions | 0..50°C, 0..85% rh non-condensing |
| 36A all relays | |
| Power supply | 24V (18..28V), 260mA |
| (20mA+11mA*active outputs+9mA*active inputs) | |
| Weight | 360g |
| Degree of protection | IP20 |
| Level of ambient pollution | 2 |
| Standards | EN 61010-1, EN 61010-2-201, EN 61131-2 |
Terminals
Dimensions
hiq/components/bio-8r4.txt · Last modified: by alen.mejak