AoV-12

Voltage outputs, 12 x 0…10V

aov-12_main_picture.jpg

Model number: AoV-12
Mounting: DIN rail

Features

  • IEX-2 module
  • 12 12 analog outputs 0..10V

Technical specification

Output type 0..10V
Output current max. 10mA per chanel
max. 70mA for all chanels
8 bits
Accuracy 1% of FSR
Temperature drift +-0.01%/°C of output range
Settling time 50ms
Power supply 24V (18..28V), 120mA (50mA+output current)
Galvanic isolation 1kV between digital and analog circuit
no isolation between chanels
Operating conditions 0..50°C, 0..85% rh non-condensing
Weight 160g
Degree of protection IP20
Level of ambient pollution 2
Standards EN 61010-1, EN 61010-2-201, EN 61131-2