hiq:components:aiv-12
                Table of Contents
AiV-12
Features
- IEX-2 module
 - 12 analog inputs 0…10V
 
Technical specification
| Input type | 0..10V | 
| Input resistance | 10K | 
| A/D converter | V/f conversion with auto calibration | 
| Resolution | 13 bits in 0.1% mode | 
| 11 bits in 0.5% and 1% mode | |
| Temperature drift | +-0.01%/°C of measuring range | 
| Scan time | 30ms..980ms, depends on input mode | 
| Integration time | 60ms/20ms, depends on input mode | 
| Calibration reference | 10.000V | 
| Power supply | 24V (18..28V), 50mA | 
| Galvanic isolation | 1kV between digital and analog circuit | 
| no isolation between chanels | |
| Operating conditions | 0..50°C, 0..85% rh non-condensing | 
| Weight | 160g | 
| Degree of protection | IP20 | 
| Level of ambient pollution | 2 | 
| Standards | EN 61010-1, EN 61010-2-201, EN 61131-2 | 
Terminals
Dimensions
hiq/components/aiv-12.txt · Last modified:  by alen.mejak
                
                