hiq:components:aic-12
Table of Contents
AiC-12
Features
- IEX-2 module
- 12 analog inputs 0…20mA
Technical specification
Input type | 0..20mA |
Input resistance | 50ohm |
A/D converter | V/f conversion with auto calibration |
Resolution | 13 bits in 0.1% mode |
11 bits in 0.5% and 1% mode | |
Temperature drift | +-0.01%/°C of measuring range |
Scan time | 30ms..980ms, depends on input mode |
Integration time | 60ms/20ms, depends on input mode |
Calibration reference | 10.000mA |
Power supply | 24V (18..28V), 50mA |
Galvanic isolation | 1kV between digital and analog circuit |
no isolation between chanels | |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
Weight | 160g |
Degree of protection | IP20 |
Level of ambient pollution | 2 |
Standards | EN 61010-1, EN 61010-2-201, EN 61131-2 |
Terminals
Dimensions