MODBUS
Address range: | 220..235 |
Data bits & parity: | 8n1 |
Supported functions: | 01 – read coils |
04 – read input registers | |
05 – write single coil | |
15 – write multiple coils |
RELAY OUTPUT
Nominal rating: | 5A 250VAC resistive |
Timeout: | 24h (reset if no messages) |
TEMPERATURE SENSOR
Input type: | ES digital sensor DS18B20 |
Connection protocol: | 1-wire digital thermometer |
Sensor error | -1000: missing, -1001: short |
Measuring range | -50..+125°C |
Accuracy | ±0.5°C (-10°C to +85°C) |
Cable length | 50m, UTP 0.25..0.5mm2 |
RADIO
Frequency band: | ISM 868MHz (EU) |
Subband: | L 866.8MHz, 25mW, 1% utility |
Modulation | FSK 38.4kbps 80kHz bandwidth |
Group address | 32-bit, automatically generated |
Listen before talk | yes, delay limited to 20ms |
Startup time | 10s power-on to network ready |
Message delay | 5ms from tx start to relay on |
Operating range | 300m with optical visibility |
Output power | 25mW |
GENERAL
Power supply | 230V, 50..60Hz, 3.5W |
Terminals | 0.25..2.5mm2 |
Operating conditions | -20..+50°C, 0..85% rh nc |
Storage temperature | -40..+85°C |
Weight | 220g |
Degree of protection | IP20 |
Standards | EN60730-1, EN300-220-2, EN 301 489-1, EN 301 489-3 |