DALI output current | 200mA |
Ballasts per device | 64 (2mA per device) |
Bus length | 300m |
Galvanic isolation | 3kV, DALI to digital ground |
Surge protection | 4kW (8/20us), 30kV/150pF |
Autoaddress | no |
Typical usage | office buildings and halls |
Duty cycle | 1:10 (DALI active 10% of the time) |
Load protection | short-circuit and thermal shutdown |
230V tolerance | no |
Input type | dry contact, internal pull-up 12V 2mA |
Power supply | 24V (18..28V), 200mA |
Operating conditions | 0..45°C, 0..95% rh non-condensing |
Storage temperature | -20..75°C |
Degree of protection | IP20 |
Weight | 120g |
Standards | EN 60730-1, EN 61000-4-4 |