10 dig inputs, 10 relay 8A outputs

bio-20r_main_picture.jpg

Model number: Bio-20R
Mounting: DIN rail, 6M, 106 mm

Features

Technical specification

Input type dry contact, internal pull-up 12V 2mA
Output type relay 8A/250VAC or 8A/30VDC resistive
Contact type normally open
Continuous load 6A each relay
20A all relays (mk1)
12A each relay group (mk2)
Power supply 24V (18..28V), 120mA
(30mA+9mA*number of active outputs)
Galvanic isolation 4kV between internal circuit and relay contact
Operating conditions 0..50°C, 0..85% rh non-condensing
36A all relays
Power supply 24V (18..28V), 260mA
(20mA+11mA*active outputs+9mA*active inputs)
Weight 300g
Degree of protection IP20
Level of ambient pollution 2
Standards EN 60730-1

Terminals

Dimensions