====== Hardware ====== |< 1200px 120px 200px 300px >| ^ Code ^ Description ^ Quantity ^ Note ^ ^ Basic | **Required for basic functionality** ||| ^ [[wiki:01_btms:00_hw:01_bm-gw]] | BTMS IOT Gateway | 1 × BM-GW for up to 32 strings | All strings of one UPS should be on the same BM-GW | ^ [[wiki:01_btms:00_hw:02_bm-ss]] | BTMS String master | 1 × BM-SS for each string | | ^ [[wiki:01_btms:00_hw:03_bm-hs]] | BTMS Hall sensor | 1 × BM-HS for each string | Choose the type based on the maximum string current | ^ [[wiki:01_btms:00_hw:04_bm-cs]] | BTMS Cell sensor | 1 × BM-CS for each battery | Choose 2, 6 or 12 V sensors depending on the battery voltage | ^ [[wiki:01_btms:00_hw:05_bm-ps]] | BTMS Power supply | 1 × PS-60-24 for each BTMS | One power supply can power several devices, if there are fewer of them than allowed according to thespecification. Checks against the total consumption of powered devices. | ^ [[wiki:01_btms:00_hw:05_ps-30-12]] | BM-GW Power supply | 1 × PS-30-12 for each BM-GW | | ^ Optional | **Depending on requirements** ||| ^ [[wiki:01_btms:00_hw:06_bm-mc]] | BTMS Master controller | 1 × BM-MC for up to 32 strings | | ^ [[wiki:01_btms:00_hw:06_bm-c-A1]] | BTMS Controller set | 1 × BM-C-A1 for up to 32 strings | Consisting of [[wiki:01_btms:00_hw:06_bm-mc]], [[wiki:01_btms:00_hw:07_bm-cad]] and software | ^ [[wiki:01_btms:00_hw:07_bm-cad]] | BTMS COM converter | 1 × BM-CAD per BM-HMI | They require BM-MC | ^ [[wiki:01_btms:00_hw:07_bm-com]] | BTMS COM module | 1 × BM-COM for up to 16 BM-CS | For more than 16 BM-CS (up to 32) use 2nd BM-COM | ^ [[wiki:01_btms:00_hw:07_bm-lc]] | BTMS IO expansion module | 1 × BM-LC for up to 8 strings | They require BM-MC | ^ [[wiki:01_btms:00_hw:08_bm-th]] | BTMS Temperature and humidity sensor | 1 × BM-TH for every string | They require BM-MC | ^ [[wiki:01_btms:00_hw:08_bm-gs]] | BTMS Insulation monitoring sensor | 1 × BM-GS for every string | They require BM-MC and BM-COM | ^ [[wiki:01_btms:00_hw:09_bm-hmi]] | BTMS Human-Machine Interfaces | 1 × BM-HMI for up to 32 strings | They require BM-C-A1 (BM-MC + BM-CAD), 1 per BM-C-A1 | ^ [[wiki:01_btms:00_hw:10_bm-ag]] | BTMS IOT Aggregator | 1 × BM-AG per Data center | Needed when there are multiple BM-GWs on the Data Center | ^ [[wiki:01_btms:00_hw:06_th-mc]] | Temperature and humidity monitoring Master controller | 1 × TH-MC for up to 120 temperature-humidity sensors | | ^ [[wiki:01_btms:00_hw:06_tm-c-A1]] | Temperature and humidity monitoring Controller set | 1 × TH-MC for up to 120 temperature-humidity sensors | Consisting of [[wiki:01_btms:00_hw:06_th-mc]], [[wiki:01_btms:00_hw:07_bm-cad]] and software | ===== System limitations ===== |< 700px 100px >| ^ Device ^ Supports up to ^ | BM-AG | unlimited BM-GW | | BM-GW | 32 × BM-SS, 1 × BM-MC | | BM-MC | 32 × BM-TH, 4 × BM-LC, 1 × BM-HMI | | BM-SS | 120 × BM-CS |