====== PM1-E-D ======
**Single phase power-sensor**
{{ hiq_components:pm1-e-d_main_picture.png |}}
| Model number: ^ PM1-E-D |
| ::: | RS485 power sensor bus A - B |
| Mounting: | DIN rail, 1M |
^ Used for measuring power and energy of ||
| ✔ | single-phase energy sources |
| ✔ | single-phase energy consumers |
===== Applications =====
* Digital multi-function power-sensor for single phase networks
===== Features =====
* DIN rail mounting with direct connection up to 45A
* Compact design in a single module 18mm wide
* Seal-able cover(phase and neutral terminals)
===== General description =====
The PM1-E-D series is an advanced single phase energy monitoring solution with built-in configuration push button and LCD data display. Particularly indicated for metering active energy and other power parameters. Housing for DIN-rail mounting, IP51 protection degree, direct connection up to max 45A.
===== Technical specifications =====
|< 40% 50% >|
^ Energy Measurements ||
| Imported/Exported active energy | 0 to 99999.99 kWh |
| Imported/Exported reactive energy | 0 to 99999.99 kVArh |
| Total active energy | 0 to 99999.99 kWh |
| Total reactive energy | 0 to 99999.99 kVArh |
^ Measured Inputs ||
| Nominal Voltage Input | (Ph+N) 176 to 276V |
| Max Continuous Voltage | 120% of nominal |
| Nominal Input Current | 5(45)A |
| Max Continuous Current | 120% of nominal |
| Frequency | 50Hz (±10%) |
^ Accuracy ||
| Voltage | 0·5% of range maximum |
| Current | 0·5% of nominal |
| Frequency | 0·2% of mid-frequency |
| Power factor | 1% of unity (0.01) |
| Active power (W) | ±1% of range maximum |
| Reactive power (VAr) | ±1% of range maximum |
| Apparent power (VA) | ±1% of range maximum |
| Active energy (Wh) | Class 1 IEC 62053-21 |
| Reactive energy (VARh) | ±1% of range maximum |
^ Modbus (RS485 Output for Modbus RTU & Pulsed Output) ||
| Baud rate | 1200, 2400, 4800, 9600. |
| Parity | none / odd / even |
| Stop bits | 1 or 2 |
| RS485 network address | 1 to 247 |
^ Reference Conditions of Influence Quantities ||
| Ambient temperature | 23°C ±1°C |
| Input waveform | 50 or 60Hz ±2% |
| Input waveform | Sinusoidal (distortion factor < 0·005) |
| Auxiliary supply voltage | Nominal ±1% |
| Auxiliary supply frequency | Nominal ±1% |
| Auxiliary supply waveform (if AC) | Sinusoidal (distortion factor < 0·05) |
| Magnetic field of external origin | Terrestrial flux |
^ Environment ||
| Operating temperature | -25°C to +55°C |
| Storage temperature | -40°C to +70°C |
| Relative humidity | 0 to 95%, non-condensing |
| Altitude | Up to 3000m |
| Warm up time | 1 minute |
| Vibration | 10Hz to 50Hz, IEC 60068-2-6, 2g |
| Shock | 30g in 3 planes |
^ Mechanics ||
| DIN rail dimensions | 18mm x 90mm (WxH) per DIN 43880 |
| Mounting | DIN rail (DIN 43880) |
===== Terminals =====
{{hiq_components:pm1-e-d_terminals.png |}}
===== Dimensions =====
{{hiq_components:pm1-e-d_dimensions.png |}}
===== Download =====
{{hiq_components:hiq_pm1-e-d_user_manual_2020.pdf |}} {{hiq_components:hiq_pm1-e-d-modbus_protocol_v2.2.pdf |}}