====== AiR-12 ======
** Resistive inputs (RTD) 12xPt100/1000, Ni100/1000 or potentiometer **
{{hiq_components:air-12_main_picture.jpg}}
| Model number: ^ AiR-12 |
| Mounting: | DIN rail |
===== Features =====
* IEX-2 module
* 12 RTD inputs
===== Technical specification =====
| Input type | Pt100/1000 (DIN751) auto selectable, measuring range -100..300°C|
| | Ni100/1000 (DIN43760) auto selectable, measuring range -50..160°C|
| | Ni100/1000 (Landis & Gyr) auto selectable, measuring range -50..160°C|
| | potentiometer 0..2000ohm|
| Sensor current | 190uA (each sensor)|
|Wire resistance | 20ohm max. (3-wire mode)|
|Resolution | 14 bits in 0.1% mode|
| | 12 bits in 0.5% and 1% mode|
| Temperature drift | +/-0.01%/°C of measuring range|
| Scan time | 30ms..980ms, depends on input mode|
| Calibration reference | 150.00ohm, 1500.0ohm|
|Power supply | 24V (18..28V), 50mA|
| Galvanic isolation | 1kV between digital and analog circuit|
| | no isolation between chanels|
| Operating conditions | 0..50°C, 0..85% rh non-condensing|
| Weight | 160g|
| Degree of protection | IP20|
| Level of ambient pollution | 2|
| Standards | EN 61010-1, EN 61010-2-201, EN 61131-2|
===== Terminals =====
{{hiq_components:air-12_terminals.png}}
===== Dimensions =====
{{hiq_components:air-12_dimensions.png}}