wiki:20_rdc_charger:35_commissioning:06_ev_fleet
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
wiki:20_rdc_charger:35_commissioning:06_ev_fleet [2023/05/26 13:04] – external edit 127.0.0.1 | wiki:20_rdc_charger:35_commissioning:06_ev_fleet [2025/03/21 13:07] (current) – saso.santelj | ||
---|---|---|---|
Line 2: | Line 2: | ||
- | RDX charger supports connection of up to 8 RDX Chargers - EV fleet.\\ | + | RDC charger supports connection of up to 8 RDC Chargers - EV fleet.\\ |
- | In such configuration only one RDX Charger (master) is in charge of other connected chargers (slave).\\ | + | In such configuration only one RDC Charger (master) is in charge of other connected chargers (slave).\\ |
- | Master | + | Master |
* current draw by other slave chargers and in real time allocates (limits) available capacity allowing them to charge without overloading, | * current draw by other slave chargers and in real time allocates (limits) available capacity allowing them to charge without overloading, | ||
- | * data from slaves such as power, energy & settings and synchronize them with cloud service, therefore no need for extra [[wiki: | + | * data from slaves such as power, energy & settings and synchronize them with cloud service, therefore no need for extra [[wiki: |
**Note:** If there is no grid power sensor, master charger enables limiting of complete ev fleet by virtual grid power sensor.\\ | **Note:** If there is no grid power sensor, master charger enables limiting of complete ev fleet by virtual grid power sensor.\\ | ||
- | :!: Only one RDX charger is master in ev fleet ! | + | :!: Only one RDC charger is master in ev fleet ! |
- | === Procedure to set RDX Charger as slave is as follows: === | + | === Procedure to set RDC Charger as slave is as follows: === |
- | * [[wiki: | + | * [[wiki: |
- | * RDX Charger -> enable "EVSE works as slave" (2) Master SN presents serial number of master charger, it will appear once connection is established. | + | * RDC Charger -> enable "EVSE works as slave" (2) Master SN presents serial number of master charger, it will appear once connection is established. |
- | * RDX Charger -> set current if connection with master is lost (3) | + | * RDC Charger -> set current if connection with master is lost (3) |
* [[wiki: | * [[wiki: | ||
- | * HEMS Configurator -> limiter -> set "No limiter" | + | * HEMS Configurator -> limiter -> set "No limiter" |
{{wiki: | {{wiki: | ||
- | === Procedure to set RDX Charger as master is as follows: === | + | === Procedure to set RDC Charger as master is as follows: === |
- | * [[wiki: | + | * [[wiki: |
{{wiki: | {{wiki: | ||
* HEMS Configurator -> settings -> enter name and select icon (2). Message "Error - device is not responding" | * HEMS Configurator -> settings -> enter name and select icon (2). Message "Error - device is not responding" | ||
Line 25: | Line 25: | ||
* HEMS Configurator -> limiter: | * HEMS Configurator -> limiter: | ||
* (3) enter allowed current value of grid fuses in case of connected grid power sensor, or max current limit of complete ev fleet if there is virtual grid active | * (3) enter allowed current value of grid fuses in case of connected grid power sensor, or max current limit of complete ev fleet if there is virtual grid active | ||
- | * (4) make sure to configure phase order for grid and RDX Chargers correct as dynamic load management may not work properly. **Double check!** | + | * (4) make sure to configure phase order for grid and RDC Chargers correct as dynamic load management may not work properly. **Double check!** |
* (5) select limiter priority for chargers: no limiter, limit last (last to be limited), limit second, limit first (first to be limited) | * (5) select limiter priority for chargers: no limiter, limit last (last to be limited), limit second, limit first (first to be limited) | ||
{{wiki: | {{wiki: | ||
- | * HEMS Configurator -> IO mux -> enter IP address of slave RDX Charger (6). Serial number (SN) will be listed automatically once connection is established. | + | * HEMS Configurator -> IO mux -> enter IP address of slave RDC Charger (6). Serial number (SN) will be listed automatically once connection is established. |
{{wiki: | {{wiki: | ||
- | * HEMS Configurator -> ev fleet:\\ (7) master | + | * HEMS Configurator -> ev fleet:\\ (7) master |
{{wiki: | {{wiki: |