Wireless Modbus Relay

Wireless Modbus Relay

Model number: WR-1
Frequency: ISM 868MHz (EU)
Dimensions: 93x45x27 mm

Applications

  • Remote controlled relay. Act as modbus RTU slave. Optimal for long range, no hopping.

Installation and mounting

Features

Technical specification

Power supply: 230V, 50/60Hz, 1W
Ingress protection: IP20
Operating temperature: -20..50°C
Storage temperature: -40..85°C
Relative humidity: 0..85% n/c

Modbus

Address range: 200..207
Relay mapping coil 1(start address 00h)
Data bits & parity 8n1
Supported functions 01 - read coil
05 - write single coil
15 - write multiple coils

Relay output

Nominal rating 10A 250Vac (NO), 3A 250Vac (NC)
(resistive) 5A 30Vdc (NO), 3A 30Vdc (NC)

Radio

Frequency band ISM 868MHz (EU)
Subband L 866.8MHz, 25mW, 1% utility
Modulation fSK 38.4kbps 80kHz bandwidth
Listen before talk yes, delay limited to 20ms
Group address 32-bit, automatically generated
Connection time 10s power-on to network ready
Message delay 5ms from tx start to relay on
Output power 25mW
Operating range 3..300m with optical visibility

Modbus address setting

Change is applied right away, no reset needed.

Radio pairing configuration

Create new secure group

* turn on all devices as the same time
* within 10 seconds, while RF LED is blinking, press and hold button on one of the devices
* after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address.

Add new device to the group

* turn on the device
* within 10 seconds, press and hold button on one of the existing devices
* after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent.

Examples

Connection check

With each press of the button, the relay will switch on/off. Other devices are not affected.

Factory reset