Virtual serial communication module IEX - RS232 / RS485
| Model number: | V-COM |
|---|---|
| Mounting: | DIN rail, 2M, 36 mm |
V-COM is an IEX-2 communication module that provides virtual serial ports (RS-232 / RS-485) for Cybro controllers. It allows PLC programs to communicate with external devices through virtual COM interfaces while maintaining the same programming logic as physical ports.
The module connects to the IEX-2 bus and provides galvanically isolated communication with external serial devices.
| Parameter | Value |
|---|---|
| Communication interface | RS-232 / RS-485 |
| Virtual ports | COM6, COM7, COM8, COM9 |
| Baud rate | 2400 – 115200 |
| Added latency | ~100 µs per byte |
| Galvanic isolation | 1 kV |
| RS-232 cable length | up to 10 m |
| RS-485 cable length | up to 1000 m |
| Power supply | 24 V DC (18–28 V) |
| Power consumption | approx. 40 mA |
| Operating temperature | 0 – 50 °C |
| Humidity | 0 – 85 % RH (non-condensing) |
| Mounting | DIN rail (35 mm) |
| Protection | IP20 |
| Dimensions | 36 × 107 × 58 mm |
| Weight | approx. 75 g |
232 and 485 ports are functionally identical. Outgoing messages are transmitted on both ports, incoming messages are received from either port.
IEX-2 terminals are used when module is installed outside the distribution board, or for connecting external devices to the board.
Typical usage
Up to 4 fully independent ports
Single virtual port with multiple devices