====== Power plant connection ====== The power plants can be connected to the grid in two ways: |< 700px >| ^ serial with grid power sensor |^ parallel with grid power sensor | | {{ wiki:20_rdc_charger:connected_power_plant_in.png?direct400 |}} || {{ wiki:20_rdc_charger:connected_power_plant_ex.png?direct400 |}} | When configuring the power plant, select ***in**: serial (**in**ternal) with grid power sensor ***ex**: parallel (**ex**ternal) with grid power sensor Power plants are configured as internal by default. Obtaining data (power, voltage, etc...) from power plants is possible in two ways:\\ 1. adding [[wiki:20_rdc_charger:35_commissioning:01_power_sensor|power sensor]] to measure produced electricity\\ 2. connecting PV inverter via Modbus TCP (for SolarEdge inverters only) === EVSE and PV inverter connection === |< 700px >| | {{ wiki:20_rdc_charger:rc_pv_inverter_connection_router.png?direct&800|}} | Add inverter using configurator: * [[wiki:20_rdc_charger:30_software:start#settings|settings]] page -> meter -> select 'SolarEdge', {{wiki:20_rdc_charger:pv_settings_01.png?direct&700|}}\\ * [[wiki:20_rdc_charger:30_software:start#io_mux|io mux]] page -> Slave device IP address -> IP address -> set IP address of inverter (inverter must have static IP) {{wiki:20_rdc_charger:pv_settings_02.png?direct&300|}} Setup Modbus TCP on Inverter side using SolarEdge SetApp: * Select Site Communication menu * RS485-1 -> Protocol -> SunSpec (Non-SE Logger) * RS485-1 -> Device ID, enter address 1 * Modbus TCP -> Enable * set TCP port -> 502 **Note**:\\ The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes.\\ First, add inverter to Configurator, then setup Inverter by SetApp!