====== BTMS - Battery Monitoring System ====== BTMS is a battery monitoring system for larger UPS systems. Enables: * cell status monitoring * equalization of cell load within the string * switching off strings where an error is detected on at least one cell ===== Dictionary of terms and abbreviations ===== |< 1200px 150px 250px >| ^ BTMS | Batery Monitoring System | Battery monitoring system for larger UPS systems. | ^ battery | - | Lead-acid rechargeable battery stores electricity to operate the UPS during a power outage. | ^ cell | - | Basic battery building. A battery usually consists of several cells connected in series. | ^ string | - | Multiple batteries connected in series. | ^ UPS | Uninterruptible Power Supply | A device that provides battery backup when the electrical power fails or drops to an unacceptable voltage level. | ^ BM-AG | BTMS Aggregator | When several BM-GW's are needed at the Datacenter, aggregate all BM-GW and provide site functionality + Cloud connectivity and alarming.' | ^ BM-GW | BTMS Gateway | Visualization (browser) of batteries and installed systems connected to the GW logically grouped into strings and UPS's in real time and their historical data. Alarming, Cloud connectivity | ^ SCADA | 3rd party SCADA | Any SCADA that accesses battery, stringig and/or UPS data via Modbus TCP/IP protocol. | ^ PC web | PC with WEB Browser | Viewing the user interface from BM-AG or BM-GW via any web browser. | ^ BM-MC | BTMS Master Controller | It allows the connection of BM-TH sensors and configurable digital inputs for monitoring additional alarm signals and outputs for alarming or switching off strings where an error occurs. | ^ BM-HMI | BTMS Human-Machine Interface | Local display of the state of the batteries inside the UPS, string and by battery. | ^ CAD | BTMS HMI interface | Communication interface for connecting BM-HMI to BM-CS | ^ BM-LC | BTMS IO Module | Expansion for MC with additional digital inputs and outputs. | ^ BM-TH | BTMS Temperature and Humidity sensor | Ambient temperature and relative humidity sensor. | ^ BM-GS | BTMS Insulation monitoring sensor | String insulation resistance monitoring | ^ BM-SS | BTMS String Master | It monitors the string (string current), aggregates battery data (total string voltage, average SOC, Balance) and enables monitoring of data from BM-CSs. | ^ BM-HS | BTMS Hall Sensor | It measures the string current | ^ BM-CS | BTMS Cell / Battery Sensor | Control of each individual battery / cell. It allows monitoring the status, voltage, internal resistance, temperature of the cell and calculates SOC and SOH. | ^ SOC | State Of Charge | Calculated battery charge; it is calculated from the actual voltage on the battery and by integrating the charge and discharge current. | ^ SOH | State Of Health | Informative battery state calculation that takes into account internal resistance, battery temperature, rise/fall of voltage during charge/discharge and other parameters that affect battery performance. | ^ Balance | Voltage balance within string | Calculation of voltage inequality on the batteries within the string. Battery sensors can actively equalize the voltage between the batteries within the string during the floating charge phase. | ===== System diagram ===== {{:wiki:01_btms:sch.svg|}} ===== Wiring diagram ===== {{:wiki:01_btms:sch_v4.png?direct|}} ===== Detailed Wiring diagram ===== {{ wiki:01_btms:00_hw:wiring_diagram_bm-ca-36_20240620.pdf | Detailed Wiring diagram }}