====== 3-ph current transformer ======
**Split core current transformer 50A - 400A **
{{ wiki:20_rdc_charger:03_hardware:ct_main_picture.png |}}
| Model number: ^ CT3-E-50 | 50A |
| ::: ^ CT3-E-100 | 100A |
| ::: ^ CT3-E-250 | 250A |
| ::: ^ CT3-E-400 | 400A |
| Connect to: | [[wiki:20_rdc_charger:15_hardware:21_pm3-ct|PM3-E-D-CT]] ||
| ::: | terminals 15 - 20 ||
| Mounting: | on wire ||
* Split core
* Safe operation
* Small size
* Very easy mounting
* Wide inner window
===== General description =====
The CT-3-E-xx split core current transformer is designed for fast and easy installation. The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken off line and disconnected for CT installation. This method permits a safer easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary circuit.
===== Technical specifications =====
|< 50% 50% >|
| Frequency | 50-60 Hz |
| Rated current | 50 A -400 A|
| Accuracy | ±1% from 20% to 120% of rated current |
| Phase angle | less than 2 degrees at 50% of rated current |
| Insulation voltage | 600 VAC |
| Maximum primary voltage | 5000 VAC (insulated conductor) |
| Dielectric strength | 2.5 kV/1mA/1min |
| Operating temperature | -15 to 60°C |
| Operating humidity | < 85 % |
| Case material | PC/UL94-V0 |
| Bobin | PBT |
| Core | Permalloy |
| Internal structure | Epoxy |
| Leads | UL 1015, Twisted pair, 22 AWG |