====== BM-LC ======
**BTMS IO expansion module**
{{wiki:01_btms:media:00_hw:bm-lc.png?nolink&400|}}
| Model number: ^ BM-LC ^
| Mounting: | DIN rail, 6M, 106 mm |
| Dimensions: | 106×108×58 mm |
===== Applications =====
* Expansion for MC with additional digital inputs and outputs
* Additional sensors (leak, gas) can be connected to inputs
* Relay outputs can disconnect faulty string or turn on additional signaling in the event of an error on the string
===== Technical specification =====
| Output power per relay | |
| - incandescent / halogen 230V | 1000 W|
| - halogen 12V with transformer | 500 W|
| - LED with transformer or compact | 500 W|
| Total power for all outputs together: | 4000 W|
| Maximum switching voltage | 250Vac|
| Dielectric strength output to output | 400Vac|
| Maximum input cable length: | 50 m|
| Power supply: | 24 V / max. 120 mA|
| Ingress protection: | IP20|
| Operating temperature: | 0..45 °C|
| Storage temperature: | -20..75 °C|
| Relative humidity: | 0..95 % n/c|
| Weight: | 280g|
===== Terminals =====
{{wiki:01_btms:media:00_hw:bm-lc_terminals.png?nolink|}}