====== V3 - GRMS Room Compact Modbus - MC-230-01 ====== ===== General description ===== **V3 - GRMS Room Compact Modbus - MC-230-01** is a compact GRMS room variant based on the **MC-230-01** controller. This variant is intended for simplified room configurations where integrated RS485 communication and direct IEX connection are required. Because MC-230-01 includes RS485 and IEX-2 terminals, separate CAD-BC and CAD-232 modules are not required for this room concept. ===== Typical use ===== This variant is suitable for rooms requiring: * compact controller configuration * integrated RS485 / Modbus communication * direct IEX connection * basic access and room panel functionality * HVAC control with reduced local I/O requirements * simplified installation compared to MC-24-H1 based configurations * Ethernet / Linker connection to S-RMS ===== Main components ===== ^ Group ^ Component code ^ Description ^ | Room controller | **MC-230-01** | Main room controller with integrated Ethernet, RS485 and IEX-2 terminals. | | Power supply | **230 VAC / MC-230-01 supply** | Controller supply. Only one supply option is used according to project configuration. | | IEX connection | **MC-230-01 IEX-2 terminals** | Direct IEX device connection without CAD-BC module. | | RS485 / Modbus | **MC-230-01 RS485** | Integrated RS485 communication for Modbus fan-coil, recuperator or compatible HVAC equipment. | | Corridor access panel | **CR-D1-V2-PX-BK** | Corridor-side access panel for room access, door status and lock control. | | Door lock | **EL-B / EL-N** | Electric door strike, selected according to door type and installation requirements. | | Room touch panel assembly | **TGP-4D-01-IQ + TGP-S** | In-room 4 inch touch HMI panel with TGP-S adapter/interface board for connecting the ES-W2 room temperature sensor. | | Room temperature sensor | **ES-W2-WH / ES-W2-BK** | Room temperature sensor connected through TGP-S and used for HVAC regulation. | | Room PIR sensor | **IR-R-IW-WH / IR-R-OW-WH** | Presence / motion sensor for occupancy and energy-saving logic. | | Window contact | **MOS-03-HD-WH / MOS-04-VS-WH / MOS-04-VS-BK** | Wired magnetic opening sensor for window status and HVAC interlock, if wired version is used. | | HVAC outputs | **MC-230-01 outputs / RS485** | HVAC control through local outputs or RS485 communication, depending on equipment. | | Network | **Ethernet / Linker** | Connection to S-RMS. | ===== Connected room functions ===== ^ Function ^ Connected elements ^ | Access control | CR-D1-V2-PX-BK, EL-B / EL-N and door status. | | Guest interface | TGP-4D-01-IQ room touch panel with TGP-S adapter and room commands. | | Room temperature | ES-W2-WH / ES-W2-BK connected through TGP-S. | | HVAC | RS485 / Modbus HVAC device or local HVAC outputs, depending on equipment. | | Room sensing | ES-W2 room temperature sensor, PIR sensor and window status. | | Energy saving | Presence detection, managed power supply and HVAC interlock logic. | | Central system | Ethernet connection to Linker and S-RMS. | ===== Variant difference ===== Compared to MC-24-H1 based variants, V3 uses **MC-230-01** with integrated **RS485** and direct **IEX-2 terminals**. This reduces the need for separate CAD communication modules. ===== Notes ===== * V3 is recommended for compact room configurations with limited local I/O requirements. * TGP-S is part of the room touch panel assembly and is used as the interface board for connecting the ES-W2 room temperature sensor. * It is suitable when RS485 / Modbus communication is required and the MC-230-01 I/O capacity is sufficient. * Final equipment compatibility must be checked per project.