====== WR-5 ====== **Wireless Modbus relay** {{hiq_components:wr-5_main_picture.png }} |Model number: ^ WR-5| ===== Features ===== * wireless fan-coil controller * 5 remote controlled relays * 1 temperature sensor input * 1 digital input, dry contact * modbus RTU slave protocol * very long range, no hopping * up to 16 devices per group * multiple addressable groups * protected private connection ===== Technical specification ===== MODBUS | Address range: | 220..235 | | Data bits & parity: | 8n1 | | Supported functions: | 01 – read coils | | | 04 – read input registers | | | 05 – write single coil | | | 15 – write multiple coils | RELAY OUTPUT | Nominal rating: | 5A 250VAC resistive | | Timeout: | 24h (reset if no messages) | TEMPERATURE SENSOR | Input type: | ES digital sensor DS18B20 | | Connection protocol: | 1-wire digital thermometer | | Sensor error | -1000: missing, -1001: short | | Measuring range | -50..+125°C | | Accuracy | ±0.5°C (-10°C to +85°C) | | Cable length | 50m, UTP 0.25..0.5mm2 | RADIO | Frequency band: | ISM 868MHz (EU) | | Subband: | L 866.8MHz, 25mW, 1% utility | | Modulation | FSK 38.4kbps 80kHz bandwidth | | Group address | 32-bit, automatically generated | | Listen before talk | yes, delay limited to 20ms | | Startup time | 10s power-on to network ready | | Message delay | 5ms from tx start to relay on | | Operating range | 300m with optical visibility | | Output power | 25mW | GENERAL | Power supply | 230V, 50..60Hz, 3.5W | | Terminals | 0.25..2.5mm2 | |Operating conditions | -20..+50°C, 0..85% rh nc | |Storage temperature | -40..+85°C | |Weight | 220g | |Degree of protection | IP20 | |Standards | EN60730-1, EN300-220-2, EN 301 489-1, EN 301 489-3 | ===== Dimensions and mounting ===== {{:hiq_components:wr-5_dimensions.png?600|}} ===== Terminals ===== {{:hiq_components:wr-5_terminals.png?600|}} ===== Examples ===== {{:hiq_components:wr-5_examples.png?770|}}