-====== Three phase power sensor, CT ====== 
- 
-**3-phase power-sensor, current transformer** 
- 
-<WRAP column 350px> 
- 
-{{  wiki:20_rdc_charger:03_hardware:pm3-e-d_ct.png?nolink  |}} 
- 
-</WRAP> 
- 
-<WRAP column 300px> 
- 
-| Model number: ^ PM3-E-D-CT                                   | 
-| Connect to:   | [[wiki:20_rdc_charger:15_hardware:01_rdx_charger]]           | 
-| :::           | RS485 power sensor bus A - B                 | 
-| Mounting:     | DIN rail, 1M, 18 mm                          | 
-| Dimensions:   | 65 × 72 × 94,5 mm                              
- 
-^ Used for measuring power and energy of                 || 
-| ✔ | single/three-phase energy sources                        | 
-| ✔ | single/three-phase energy consumers                      | 
- 
-</WRAP> 
- 
-<WRAP clear></WRAP> 
- 
-===== Applications ===== 
- 
-  * Digital multi-function power sensor for single/three phase networks 
- 
-===== Features ===== 
- 
-  * DIN rail mounting with 3x current transformers ([[ wiki:20_rdc_charger:15_hardware:21_ct-3-e-xx |3-ph current transformer]]) 
-  * Line voltage and THD% (total harmonic distortion) of all phases 
-  * Line Frequency 
-  * Currents, Current demands and current THD% of all phases 
-  * Power, maximum power demand and power factor 
-  * Active energy imported and exported 
-  * Reactive energy imported and exported 
- 
-===== General description ===== 
- 
-The unit measures and displays the characteristics of three phase four wires(3p4w) supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported. 
- Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60minutes.  
-In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product.  
-The requisite current input(s) are obtained via current transformers (CT). 
-This power sensor can be configured to work with a wide range of CTs with 0.33V output, giving the unit a wide range of operation. Built-in interfaces provide pulse and RS485 Modbus RTU outputs. Configuration is password protected. 
-This power sensor can be powered from a separate auxiliary (AC or DC) supply. Alternatively, it can be powered from the monitored supply, where appropriate. 
- 
-===== Technical specifications ===== 
- 
-|< 35% 40% >| 
-^ Technical Data                                                               || 
-| Operating Humidity                                                    ≤ 75% | 
-| Storage Humidity                                                      ≤ 95% | 
-| Operating Temperature          |                                -25°C - +50°C | 
-| Storage Temperature            |                                -40°C - +70°C | 
-| Mounting                                               DIN rail (DIN 43880) | 
-| Sealing                        |                                  IP51 Indoor | 
-| Auxiliary supply voltage                                       Nominal ± 1% | 
-| Auxiliary supply frequency                                     Nominal ± 1% | 
-| Frequency                      |                            50Hz or 60Hz(±2%) | 
-| Power Consumption              |                                        ≤ 10W | 
-^ Accuracy                                                                     || 
-| Voltage, Current                                                       0.5% | 
-| Frequency                      |                        0.2% of Mid-Frequency | 
-| Power Factor                                             1% of Unity (0.01) | 
-| Active Power, Apparent Power                          ± 1% of Range Maximum | 
-| Reactive Power                                        ± 1% of Range Maximum | 
-| Reactive Energy (Varh)                                ± 1% of Range Maximum | 
-| Active Energy (Wh)                                      Class 1 IEC 62053-21| 
-^ Current transformer                                                          || 
-| Frequency                      |                                     50-60 Hz | 
-| Rated current                  |                                         50 A | 
-| Accuracy                                  from 20% to 120% of rated current | 
-| Phase angle                    |  less than 2 degrees at 50% of rated current | 
-| Insulation voltage                                                  600 VAC | 
-| Maximum primary voltage        |               5000 VAC (insulated conductor) | 
-| Dielectric strength            |                              2.5 kV/1mA/1min | 
-| Operating temperature          |                                  -15 to 60°C | 
-| Operating humidity                                                   < 85 % | 
-| Case material                  |                                   PC/UL94-V0 | 
-| Bobin                          |                                          PBT | 
-| Core                                                              Permalloy | 
-| Internal structure                                                    Epoxy | 
-| Leads                          |                UL 1015, Twisted pair, 22 AWG | 
-^ Modbus                                                                       || 
-| Bus Type                                                RS485 (Semi-Duplex) | 
-| Protocol                                                         Modbus RTU | 
-| Baud Rate                      |                       1200/2400/4800/9600bps | 
-| Address Range                  |                                        1-247 | 
-| Max. Bus Loading                                                      64pcs | 
-| Communication Distance                                          1000 Meters | 
-| Parity                                                        EVEN/ODD/NONE | 
-| Data Bit                                                                  8 | 
-| Stop Bit                                                                  1 | 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-<WRAP pagebreak></WRAP> 
- 
-===== Dimensions ===== 
- 
-{{wiki:20_rdc_charger:03_hardware:pm3-e_ct_dimensions.png?nolink|}} 
- 
-===== Installation ===== 
- 
-{{wiki:20_rdc_charger:03_hardware:pm3-e_instalation.png?nolink|}} 
- 
-{{ wiki:20_rdc_charger:03_hardware:hiq_pm3-e-d-ct_user_manual_v1.pdf |}} {{ wiki:20_rdc_charger:03_hardware:hiq_pm3-e-d-ct_protocol_v1.6.pdf |}} 
- 
- 
- 
  