User Tools

Site Tools


wiki:20_rdc_charger:15_hardware:21_ct-1-e-50

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

wiki:20_rdc_charger:15_hardware:21_ct-1-e-50 [2023/11/24 11:13] – created saso.santeljwiki:20_rdc_charger:15_hardware:21_ct-1-e-50 [2023/11/24 11:22] (current) – removed saso.santelj
Line 1: Line 1:
-====== 1-ph current transformer ====== 
- 
-**Split core current transformer 50A ** 
- 
-<WRAP column 350px> 
- 
-{{ wiki:20_rdc_charger:03_hardware:ct.png?nolink |}} 
- 
-</WRAP> 
- 
-<WRAP column 300px> 
- 
-| Model number: ^ CT-1-E-50                                           | 
-| Connect to:   | [[wiki:20_rdc_charger:15_hardware:20_pm1-ct]]       | 
-| :::           | terminals 1 -2                                      | 
-| Mounting:     | on wire                                             | 
-| Dimensions:   | 41 × 24 × 27 mm                                      
- 
-</WRAP> 
- 
-<WRAP clear></WRAP> 
- 
-  * Split core 
-  * Safe operation 
-  * Mini in size 
-  * Very easy mounting 
-  * Wide inner window 
- 
-===== General description ===== 
- 
-The CT1-E-50 split core current transformer is designed for fast and easy installation. The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken off line and disconnected for CT installation. This method permits a safer easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary circuit. 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Technical specifications ===== 
- 
-|< 50% 50% >| 
-| Frequency                                                      50-60 Hz | 
-| Rated current                                                      50 A | 
-| Accuracy                  |         ±1% from 20% to 120% of rated current | 
-| Phase angle                 less than 2 degrees at 50% of rated current | 
-| Insulation voltage        |                                       600 VAC | 
-| Maximum primary voltage                  5000 VAC (insulated conductor) | 
-| Dielectric strength                                     2.5 kV/1mA/1min | 
-| Operating temperature                                       -15 to 60°C | 
-| Operating humidity        |                                        < 85 % | 
-| Case material                                                PC/UL94-V0 | 
-| Bobin                                                               PBT | 
-| Core                      |                                     Permalloy | 
-| Internal structure        |                                         Epoxy | 
-| Leads                                     UL 1015, Twisted pair, 22 AWG | 
  
wiki/20_rdc_charger/15_hardware/21_ct-1-e-50.1700824393.txt.gz · Last modified: by saso.santelj