 |< 900pt 150pt 75pt 90pt 50pt 50pt 50pt 100pt >| |< 900pt 150pt 75pt 90pt 50pt 50pt 50pt 100pt >|
-^  var          Unit ID  ^  address  ^  type  ^  scale  ^  origin                    |^  description                                                                             ^ +^  var          Unit ID  ^  address  ^  type  ^  scale  ^  origin                                  |^  description                                                                             ^ 
-| ups_status    **ui**    0        |  int    -      |  IC      | iot.ups.status   | UPS status (0 = disabled, 1 = OK (all strings OK), 2 = ERR (at least one string error)) +| ups_status    **ui**    0        |  int    -      |  IC      | iot.ups.status                 | UPS status (0 = disabled, 1 = OK (all strings OK), 2 = ERR (at least one string error)) 
-| ups_voltage  | :::        1,2      |  long  |  0.01    IC      | iot.ups.voltage  | UPS voltage (average of strings voltages) [0.01 V]                                       | +| ups_voltage  | :::        1,2      |  long  |  0.01    IC      | iot.ups.voltage                | UPS voltage (average of strings voltages) [0.01 V]                                       | 
-| ups_current  | :::        3,4      |  long  |  0.01    IC      | iot.ups.current  | UPS current (sum of string currents) [0.01 A]; + = charge, - = discharge                 | +| ups_current  | :::        3,4      |  long  |  0.01    IC      | iot.ups.current                | UPS current (sum of string currents) [0.01 A]; + = charge, - = discharge                 | 
-| ups_soc      | :::        5        |  int    1      |  IC      | iot.ups.soc      | UPS state of charge (average of strings SOC) [%]                                         |+| ups_soc      | :::        5        |  int    1      |  IC      | iot.ups.soc                    | UPS state of charge (average of strings SOC) [%]                                         
 +| alarms_sum    -        |  91,92    |  long  |  1      |  SS      | iot.data_center.active_alarms  | Sum of all alarms                                                                        |
  
 ===== Strings data ===== ===== Strings data =====