-====== Modbus TCP/IP ====== 
- 
-**Unit ID: 1** 
- 
-Supported Modbus TCP/IP function codes: 
-  * Read Holding Registers (0x03) 
-  * Write Single Register (0x06) 
-  * Write Multiple Registres (0x10) 
-===== Holding Registers===== 
- 
-|< 1200px 200px 200px 100px 100px 100px >| 
-^  Variable                                                    ^  PLC variable                  ^  Address      ^  Access  ^  Data type  ^  Description                                                                                                                                            ^ 
-^ Sensors (si=sensor index 0..120; 0=unassigned (new) sensor)                                                                                                                                                                                                                                 |||||| 
-| **Index**                                                    | si                              10 * si + 0  |  RW      |  I16        | Sensor index (si); when changed sensor will be moved to new index, but only if new space is empty                                                       | 
-| **Status**                                                   | th_status[si]                  |  10 * si + 1  |  RO      |  I16        | Temperature sensor status \\ 0 = no sensor, \\ 1 = OK, \\ 2 = Error, no response                                                                        | 
-| **Temperature**                                              | th_temperature[si]              10 * si + 2  |  RO      |  I16        | Measured temperature in 0.1 °C (234 = 23,4 °C)                                                                                                          | 
-| **Humidity**                                                 | th_humidity[si]                |  10 * si + 3  |  RW      |  I16        | Measured relative humidity in 0.1 %RH (654 = 65,4 %RH)                                                                                                  | 
-| **Alarm Temperature HI**                                     | th_temperature_alarm_hi[si]    |  10 * si + 4  |  RW      |  I16        | Measured temperature over set high limit\\ 0 = idle\\ 1 = alarm                                                                                         | 
-| **Alarm Temperature LO**                                     | th_temperature_alarm_lo[si]    |  10 * si + 5  |  RW      |  I16        | Measured temperature below set low limit\\ 0 = idle\\ 1 = alarm                                                                                         | 
-| **Alarm Humidity HI**                                        | th_humidity_alarm_hi[si]        10 * si + 6  |  RW      |  I16        | Measured humidity over set high limit\\ 0 = idle\\ 1 = alarm                                                                                            | 
-| **Alarm Humidity LO**                                        | th_humidity_alarm_lo[si]        10 * si + 7  |  RO      |  I16        | Measured humidity below set low limit\\ 0 = idle\\ 1 = alarm                                                                                            | 
-| Spare                                                        | 0                              |  10 * si + 8  |  RO      |  I16        | 0                                                                                                                                                       | 
-| Spare                                                        | 0                              |  10 * si + 9  |  RO      |  I16        | 0                                                                                                                                                       | 
-^ Statistics                                                                                                                                                                                                                                                                                  |||||| 
-| **Sensors count**                                            | th_count_all                    1210          RO      |  I16        | The number of all sensors that are configured                                                                                                           | 
-| **Sensors OK**                                               | th_count_ok                    |  1211          RO      |  I16        | The number of all sensors communicating correctly                                                                                                       | 
-| **Sensors Error**                                            | th_count_err                    1212          RO      |  I16        | Number of all sensors not responding (not communicating)                                                                                                | 
-| **Sensors Alarm**                                            | th_count_alarm                  1213          RO      |  I16        | The number of all sensors that are in alarm (temperature or humidity outside the set limits; if the limits are set)                                     | 
-| **Average temperature**                                      | th_temperature_avg              1214          RO      |  I16        | Average temperature of all sensors communicating properly                                                                                               | 
-| **Minimal temperature**                                      | th_temperature_min              1215          RO      |  I16        | The minimum temperature of all sensors communicating properly                                                                                           | 
-| **Maximal temperature**                                      | th_temperature_max              1216          RO      |  I16        | The maximum temperature of all sensors that communicate correctly                                                                                       | 
-| **Average humidity**                                         | th_humidity_avg                |  1217          RO      |  I16        | Average relative humidity of all sensors communicating correctly                                                                                        | 
-| **Minimal humidity**                                         | th_humidity_min                |  1218          RO      |  I16        | Minimum relative humidity of all sensors communicating properly                                                                                         | 
-| **Maximal humidity**                                         | th_humidity_max                |  1219          RO      |  I16        | Maximum relative humidity of all sensors communicating correctly                                                                                        | 
-| Spare                                                        | 0                              |  1220-1229    |  RO      |  i16        | 0                                                                                                                                                       | 
-^ General settings                                                                                                                                                                                                                                                                            |||||| 
-| **Temperature HI Limit**                                     | th_temperature_alarm_hi_limit  |  1230          RW      |  I16        | Limit for temperature HI alarm in 0.1 °C (500 = 50,0 °C); 0 = No temperature HI alarm                                                                   | 
-| **Temperature HI Clear**                                     | th_temperature_alarm_hi_clear  |  1231          RW      |  I16        | Limit for clear of temperature HI alarm in 0.1 °C (450 = 45,0 °C), must be lower than Temperature HI Limit; 0 = No auto clear of temperature HI alarm   | 
-| **Temperature LO Limit**                                     | th_temperature_alarm_lo_limit  |  1232          RW      |  I16        | Limit for temperature LO alarm in 0.1 °C (50 = 5,0 °C); 0 = No temperature LO alarm                                                                     | 
-| **Temperature LO Clear**                                     | th_temperature_alarm_lo_clear  |  1233          RW      |  I16        | Limit for clear of temperature LO alarm in 0.1 °C (100 = 10,0 °C), must be higher than Temperature LO Limit; 0 = No auto clear of temperature LO alarm  | 
-| **Humidity HI Limit**                                        | th_humidity_alarm_hi_limit      1234          RW      |  I16        | Limit for humidity HI alarm in 0.1 %RH (500 = 50,0 %RH); 0 = No humidity HI alarm                                                                       | 
-| **Humidity HI Clear**                                        | th_humidity_alarm_hi_clear      1235          RW      |  I16        | Limit for clear of humidity HI alarm in 0.1 %RH (450 = 45,0 %RH), must be lower than Humidity HI Limit; 0 = No auto clear of humidity HI alarm          | 
-| **Humidity LO Limit**                                        | th_humidity_alarm_lo_limit      1236          RW      |  I16        | Limit for humidity LO alarm in 0.1 %RH (50 = 5,0 %RH); 0 = No humidity LO alarm                                                                         | 
-| **Humidity LO Clear**                                        | th_humidity_alarm_lo_clear      1237          RW      |  I16        | Limit for clear of humidity LO alarm in 0.1 %RH (100 = 10,0 %RH), must be higher than humidity LO Limit; 0 = No auto clear of humidity LO alarm         | 
-| Spare                                                        | 0                              |  1238          RO      |  I16        | 0                                                                                                                                                       | 
-| Spare                                                        | 0                              |  1239          RO      |  I16        | 0                                                                                                                                                       | 
  