| + | ====== V-COM ====== | ||
| + | |||
| + | ** Virtual serial communication module IEX - RS232 / RS485 ** | ||
| + | |||
| + | <WRAP column 350px> | ||
| + | |||
| + | {{hiq_components: | ||
| + | |||
| + | </ | ||
| + | |||
| + | <WRAP column 300px> | ||
| + | |||
| + | | Model number: | ||
| + | | Mounting: | ||
| + | |||
| + | |||
| + | ===== Applications ===== | ||
| + | |||
| + | * Connecting field devices to cabinet ones | ||
| + | |||
| + | </ | ||
| + | |||
| + | <WRAP clear></ | ||
| + | |||
| + | ===== General description ===== | ||
| + | |||
| + | V-COM is an IEX-2 communication module that provides virtual serial ports (RS-232 / RS-485) for Cybro controllers. | ||
| + | It allows PLC programs to communicate with external devices through virtual COM interfaces while maintaining the same programming logic as physical ports. | ||
| + | |||
| + | The module connects to the IEX-2 bus and provides galvanically isolated communication with external serial devices. | ||
| + | |||
| + | ===== Features ===== | ||
| + | |||
| + | * Virtual serial port for PLC communication | ||
| + | * RS-232 and RS-485 interface | ||
| + | * Galvanic isolation between bus and communication port | ||
| + | * Compatible with Cybro controllers | ||
| + | * Multiple virtual COM ports available (COM6 – COM9) | ||
| + | * LED indicators for transmit and receive activity | ||
| + | * DIN-rail mounting | ||
| + | |||
| + | <WRAP pagebreak></ | ||
| + | |||
| + | |||
| + | |||
| + | ===== Technical Specifications ===== | ||
| + | |||
| + | ^ Parameter ^ Value ^ | ||
| + | | Communication interface | RS-232 / RS-485 | | ||
| + | | Virtual ports | COM6, COM7, COM8, COM9 | | ||
| + | | Baud rate | 2400 – 115200 | | ||
| + | | Added latency | ~100 µs per byte | | ||
| + | | Galvanic isolation | 1 kV | | ||
| + | | RS-232 cable length | up to 10 m | | ||
| + | | RS-485 cable length | up to 1000 m | | ||
| + | | Power supply | 24 V DC (18–28 V) | | ||
| + | | Power consumption | approx. 40 mA | | ||
| + | | Operating temperature | 0 – 50 °C | | ||
| + | | Humidity | 0 – 85 % RH (non-condensing) | | ||
| + | | Mounting | DIN rail (35 mm) | | ||
| + | | Protection | IP20 | | ||
| + | | Dimensions | 36 × 107 × 58 mm | | ||
| + | | Weight | approx. 75 g | | ||
| + | |||
| + | 232 and 485 ports are functionally identical. | ||
| + | Outgoing messages are transmitted on both | ||
| + | ports, incoming messages are received from | ||
| + | either port. | ||
| + | |||
| + | IEX-2 terminals are used when module is | ||
| + | installed outside the distribution board, or for | ||
| + | connecting external devices to the board. | ||
| + | |||
| + | {{hiq_components: | ||
| + | |||
| + | **Typical usage** | ||
| + | |||
| + | {{hiq_components: | ||
| + | |||
| + | **Up to 4 fully independent ports** | ||
| + | |||
| + | {{hiq_components: | ||
| + | |||
| + | **Single virtual port with multiple devices** | ||
| + | |||
| + | {{hiq_components: | ||
| + | |||
| + | |||
| + | ===== Bus Connection Cable ===== | ||
| + | |||
| + | {{hiq_components: | ||
| + | |||
| + | * The product includes a 2.5 cm RJ9-to-RJ9 bus cable (Order code: CAD-P0) for connection to controllers, | ||
| + | * Longer cable versions are available under order codes CAD-Px. | ||