 +====== PM1-E-D ======
  
 +**Single phase power-sensor**
 +
 +<WRAP column 450px>
 +
 +{{  hiq_components:pm1-e-d_main_picture.png  |}}
 +
 +</WRAP>
 +
 +<WRAP column 400px>
 +
 +| Model number: ^ PM1-E-D                                      |
 +| :::           | RS485 power sensor bus A - B                |
 +| Mounting:     | DIN rail, 1M                         |
 +
 +^ Used for measuring power and energy of                 ||
 +| ✔ | single-phase energy sources                        |
 +| ✔ | single-phase energy consumers                      |
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Applications =====
 +
 +  * Digital multi-function power-sensor for single phase networks
 +
 +===== Features =====
 +
 +  * DIN rail mounting with direct connection up to 45A
 +  * Compact design in a single module 18mm wide
 +  * Seal-able cover(phase and neutral terminals)
 +
 +===== General description =====
 +
 +
 +The PM1-E-D series is an advanced single phase energy monitoring solution with built-in configuration push button and LCD data display. Particularly indicated for metering active energy and other power parameters. Housing for DIN-rail mounting, IP51 protection degree, direct connection up to max 45A.
 +
 +<WRAP pagebreak></WRAP>
 +
 +===== Technical specifications =====
 +
 +|< 40% 50% >|
 +^ Energy Measurements                                                                 ||
 +| Imported/Exported active energy            |                       0 to 99999.99 kWh |
 +| Imported/Exported reactive energy          |                     0 to 99999.99 kVArh |
 +| Total active energy                        |                       0 to 99999.99 kWh |
 +| Total reactive energy                      |                     0 to 99999.99 kVArh |
 +^ Measured Inputs                                                                     ||
 +| Nominal Voltage Input                      |                      (Ph+N) 176 to 276V |
 +| Max Continuous Voltage                                             120% of nominal |
 +| Nominal Input Current                      |                                  5(45)A |
 +| Max Continuous Current                                             120% of nominal |
 +| Frequency                                  |                             50Hz (±10%) |
 +^ Accuracy                                                                            ||
 +| Voltage                                    |                   0·5% of range maximum |
 +| Current                                    |                         0·5% of nominal |
 +| Frequency                                  |                   0·2% of mid-frequency |
 +| Power factor                                                    1% of unity (0.01) |
 +| Active power (W)                                              ±1% of range maximum |
 +| Reactive power (VAr)                                          ±1% of range maximum |
 +| Apparent power (VA)                        |                    ±1% of range maximum |
 +| Active energy (Wh)                                            Class 1 IEC 62053-21 |
 +| Reactive energy (VARh)                                        ±1% of range maximum |
 +^ Modbus (RS485 Output for Modbus RTU & Pulsed Output)                                ||
 +| Baud rate                                  |                 1200, 2400, 4800, 9600. |
 +| Parity                                                           none / odd / even |
 +| Stop bits                                  |                                  1 or 2 |
 +| RS485 network address                      |                                1 to 247 |
 +^ Reference Conditions of Influence Quantities                                         ||
 +| Ambient temperature                        |                               23°C ±1°C |
 +| Input waveform                                                      50 or 60Hz ±2% |
 +| Input waveform                              Sinusoidal (distortion factor < 0·005) |
 +| Auxiliary supply voltage                                               Nominal ±1% |
 +| Auxiliary supply frequency                                             Nominal ±1% |
 +| Auxiliary supply waveform (if AC)          |   Sinusoidal (distortion factor < 0·05) |
 +| Magnetic field of external origin          |                         Terrestrial flux |
 +^ Environment                                                                         ||
 +| Operating temperature                      |                          -25°C to +55°C |
 +| Storage temperature                        |                          -40°C to +70°C |
 +| Relative humidity                          |                0 to 95%, non-condensing |
 +| Altitude                                                               Up to 3000m |
 +| Warm up time                                                              1 minute |
 +| Vibration                                  |         10Hz to 50Hz, IEC 60068-2-6, 2g |
 +| Shock                                      |                         30g in 3 planes |
 +^ Mechanics                                                                           ||
 +| DIN rail dimensions                        |         18mm x 90mm (WxH) per DIN 43880 |
 +| Mounting                                                      DIN rail (DIN 43880) |
 +