 +====== LC-DC2-ISO======
  
 +** IEX-2 module, DALI-2 application controller **
 +
 +<WRAP column 450px>
 +
 +{{hiq_components:lc-dc2_mainpicture.png}}
 +
 +</WRAP>
 +
 +<WRAP column 300px>
 +
 +| Model number: ^   LC-DC2-ISO      |
 +| Mounting:     | DIN rail |
 +
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Features =====
 +
 +
 +      * IEX-2 module
 +      * DALI-2 application controller
 +      * DALI-2 multi-master
 +      * send and receive DALI power supply
 +      * 10 digital inputs
 +      * galvanic isolation
 +      
 +     
 +      
 +<WRAP pagebreak></WRAP>
 +
 +
 +
 +===== Technical specification =====
 +
 +| DALI output current                 200mA|
 +| Ballasts per device        |   64 (2mA per device)|
 +|Bus length                           300m|
 +|Galvanic isolation      |                         3kV, DALI to digital ground|
 +|Surge protection      |                         4kW (8/20us), 30kV/150pF|
 +| Autoaddress|                         no|
 +| Typical usage                    |           office buildings and halls|
 +| Duty cycle                                       1:10 (DALI active 10% of the time)|
 +| Load protection                 |                     short-circuit and thermal shutdown|
 +|230V tolerance                |                   no|
 +|Input type                                   dry contact, internal pull-up 12V 2mA|
 +| Power supply                               24V (18..28V), 200mA|
 +|Operating conditions|                   0..45°C, 0..95% rh non-condensing|
 +| Storage temperature                  |                   -20..75°C|
 +| Degree of protection                  |                   IP20|
 +| Weight                  |                   120g|
 +| Standards                |                   EN 60730-1, EN 61000-4-4|
 +
 +===== Terminals =====
 +
 +
 +
 +<WRAP column 950px>
 +
 +{{hiq_components:lc-dc2_terminals.png}} 
 +
 +</WRAP>
 +===== Bus Connection Cable =====
 +
 +{{hiq_components:cad-px.jpg?300|}}
 +
 +  * The product includes a 2.5 cm RJ9-to-RJ9 bus cable (Order code: CAD-P0) for connection to controllers, allowing the units to be linked together.
 +  * Longer cable versions are available under order codes CAD-Px.
 +
 +===== Dimensions =====
 +
 +{{hiq_components:air-12_dimensions.png}}