User Tools

Site Tools


components:bio-8r4

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
components:bio-8r4 [2026/03/16 11:36] – removed - external edit (Unknown date) 127.0.0.1components:bio-8r4 [2026/03/16 11:36] (current) – ↷ Page moved from hiq:components:bio-8r4 to components:bio-8r4 goran.kocjancic
Line 1: Line 1:
 +====== Bio-8R4 ======
  
 +** 4x230V AC inputs, 8 relays 16A (lights) **
 +
 +<WRAP column 500px>
 +
 +{{hiq_components:bio-8r4_main_picture.PNG}}
 +
 +</WRAP>
 +
 +<WRAP column 300px>
 +
 +| Model number: ^   Bio-8r4      |
 +| Mounting:     | DIN rail, 6M, 106 mm |
 +
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Features =====
 +
 +
 +      * IEX-2 module
 +      * 4 opto-coupler inputs 230V
 +      * 8 relay outputs 16A with mains sense
 +     
 +      
 +<WRAP pagebreak></WRAP>
 +
 +
 +
 +===== Technical specification =====
 +
 +| Input type                 230VAC 1mA, opto isolated|
 +| Output type        |   relay 16A/250VAC resistive|
 +| Contact type      |                         normally open|
 +| Continuous load                             15A per relay|
 +| |                         75A for all relays together|
 +| Power supply|                        24V (18..28V), 160mA|
 +|        |                        (20mA+17mA*number of active relays)|
 +| Galvanic isolation                                    5kV between inputs and internal circuit|
 +|                                    5kV between internal circuit and relay contacts|
 +| Operating conditions                    |            0..50°C, 0..85% rh non-condensing|
 +|                |                         36A all relays|
 +| Power supply                 |                      24V (18..28V), 260mA|
 +|                  |                    (20mA+11mA*active outputs+9mA*active inputs)|
 +|Weight                    |                   360g|
 +| Degree of protection                               IP20|
 +| Level of ambient pollution                  |                   2|
 +| Standards                  |                   EN 61010-1, EN 61010-2-201, EN 61131-2|
 +
 +===== Terminals =====
 +
 +
 +
 +<WRAP column 720px>
 +
 +{{hiq_components:bio-8R4_terminals.png}} 
 +
 +</WRAP>
 +===== Bus Connection Cable =====
 +
 +{{hiq_components:cad-px.jpg?300|}}
 +
 +  * The product includes a 2.5 cm RJ9-to-RJ9 bus cable (Order code: CAD-P0) for connection to controllers, allowing the units to be linked together.
 +  * Longer cable versions are available under order codes CAD-Px.
 +
 +===== Dimensions =====
 +
 +{{hiq_components:bio-24r_dimensions.png}}