 +====== AiR-12 ======
  
 +** Resistive inputs (RTD) 12xPt100/1000, Ni100/1000 or potentiometer **
 +
 +<WRAP column 450px>
 +
 +{{hiq_components:air-12_main_picture.jpg}}
 +
 +</WRAP>
 +
 +<WRAP column 300px>
 +
 +| Model number: ^   AiR-12      |
 +| Mounting:     | DIN rail |
 +
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Features =====
 +
 +
 +      * IEX-2 module
 +      * 12 RTD inputs
 +      
 +     
 +      
 +<WRAP pagebreak></WRAP>
 +
 +
 +
 +===== Technical specification =====
 +
 +| Input type                 Pt100/1000 (DIN751) auto selectable, measuring range -100..300°C|
 +|                 Ni100/1000 (DIN43760) auto selectable, measuring range -50..160°C|
 +|              |   Ni100/1000 (Landis & Gyr) auto selectable, measuring range -50..160°C|
 +|              |  potentiometer 0..2000ohm|
 +| Sensor current        |   190uA (each sensor)|
 +|Wire resistance                           20ohm max. (3-wire mode)|
 +|Resolution      |                         14 bits in 0.1% mode|
 +| |                         12 bits in 0.5% and 1% mode|
 +| Temperature drift                    |           +/-0.01%/°C of measuring range|
 +| Scan time                                       30ms..980ms, depends on input mode|
 +| Calibration reference                |                   150.00ohm, 1500.0ohm|
 +|Power supply                                   24V (18..28V), 50mA|
 +| Galvanic isolation                               1kV between digital and analog circuit|
 +|                  |                   no isolation between chanels|
 +| Operating conditions                  |                   0..50°C, 0..85% rh non-condensing|
 +| Weight                  |                   160g|
 +| Degree of protection                  |                   IP20|
 +| Level of ambient pollution                |                   2|
 +| Standards                |                   EN 61010-1, EN 61010-2-201, EN 61131-2|
 +
 +===== Terminals =====
 +
 +
 +
 +<WRAP column 950px>
 +
 +{{hiq_components:air-12_terminals.png}} 
 +
 +</WRAP>
 +===== Bus Connection Cable =====
 +
 +{{hiq_components:cad-px.jpg?300|}}
 +
 +  * The product includes a 2.5 cm RJ9-to-RJ9 bus cable (Order code: CAD-P0) for connection to controllers, allowing the units to be linked together.
 +  * Longer cable versions are available under order codes CAD-Px.
 +
 +
 +===== Dimensions =====
 +
 +{{hiq_components:air-12_dimensions.png}}