User Tools

Site Tools


components:aic-12

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
components:aic-12 [2026/03/16 11:36] – removed - external edit (Unknown date) 127.0.0.1components:aic-12 [2026/03/16 11:36] (current) – ↷ Page moved from hiq:components:aic-12 to components:aic-12 goran.kocjancic
Line 1: Line 1:
 +====== AiC-12 ======
  
 +** Current inputs, 12 x 0...20mA **
 +
 +<WRAP column 450px>
 +
 +{{hiq_components:aic-12_main_picture.jpg}}
 +
 +</WRAP>
 +
 +<WRAP column 300px>
 +
 +| Model number: ^   AiC-12      |
 +| Mounting:     | DIN rail |
 +
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Features =====
 +
 +
 +      * IEX-2 module
 +      * 12 analog inputs 0...20mA
 +      
 +     
 +      
 +<WRAP pagebreak></WRAP>
 +
 +
 +
 +===== Technical specification =====
 +
 +| Input type                 0..20mA|
 +| Input resistance        |   50ohm|
 +|A/D converter                           V/f conversion with auto calibration|
 +|Resolution      |                         13 bits in 0.1% mode|
 +| |                         11 bits in 0.5% and 1% mode|
 +| Temperature drift                    |           +-0.01%/°C of measuring range|
 +| Scan time                                       30ms..980ms, depends on input mode|
 +| Integration time                 |                     60ms/20ms, depends on input mode|
 +| Calibration reference                |                   10.000mA|
 +|Power supply                                   24V (18..28V), 50mA|
 +| Galvanic isolation                               1kV between digital and analog circuit|
 +|                  |                   no isolation between chanels|
 +| Operating conditions                  |                   0..50°C, 0..85% rh non-condensing|
 +| Weight                  |                   160g|
 +| Degree of protection                  |                   IP20|
 +| Level of ambient pollution                |                   2|
 +| Standards                |                   EN 61010-1, EN 61010-2-201, EN 61131-2|
 +
 +===== Terminals =====
 +
 +
 +
 +<WRAP column 950px>
 +
 +{{hiq_components:aic-12_terminals.png}} 
 +
 +</WRAP>
 +===== Bus Connection Cable =====
 +
 +{{hiq_components:cad-px.jpg?300|}}
 +
 +  * The product includes a 2.5 cm RJ9-to-RJ9 bus cable (Order code: CAD-P0) for connection to controllers, allowing the units to be linked together.
 +  * Longer cable versions are available under order codes CAD-Px.
 +
 +
 +===== Dimensions =====
 +
 +{{hiq_components:air-12_dimensions.png}}