 +====== Wireless Modbus-to-Modbus bridge ======
  
 +**Wireless Modbus-to-Modbus bridge**
 +
 +<WRAP column 350px>
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_module.png?nolink |}}
 +
 +</WRAP>
 +
 +<WRAP column 300px>
 +
 +| Model number: ^ WM-1       |
 +| Frequency:    | ISM 868MHz (EU) |
 +| Dimensions:   | 93x45x27 mm     |
 +
 +===== Applications =====
 +
 +  * Replacement for RS485 wiring solution with wireless. Optimal for long range Modbus RTU serial communications with half duplex configuration.
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Installation and mounting =====
 +  * :!: Carefully open WM-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout)
 +  * :!: Place WM-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.
 +  * Connect RS485 terminals to WM-1 RS485 terminals
 +    * A - A
 +    * B - B
 +    * C - GND
 +  * Connect to 230V power supply
 +  * Bind modules to wireless network
 +
 +
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_module_diagram.png?nolink&0x500  }}
 +{{ wiki:20_rdc_charger:03_hardware:wm1_mounting.png?nolink&0x500  }}
 +
 +<WRAP pagebreak></WRAP>
 +
 +===== Features =====
 +
 +  * replacement for RS485 wiring
 +  * Modbus RTU serial protocol
 +  * wired/wireless combinations
 +  * very long range, no hopping
 +  * protected private connection
 +  * multiple slaves per device
 +  * multiple addressable groups
 +
 +
 +===== Technical specification =====
 +
 +| Power supply:          |                                230V, 50/60Hz, 1W |
 +| Ingress protection:    |                                    IP20 |
 +| Operating temperature: |                                 -20..50°C |
 +| Storage temperature:                                 -40..85°C |
 +| Relative humidity:                                  0..85% n/c |
 +
 +===== Terminals and wiring ===== 
 +
 +| To power sensor ^ A | RS485 bus  |
 +| :::            ^ B | :::        |
 +| :::            ^ C | :::        |
 +| To power supply ^ L| 230V AC |
 +| :::             ^ N| :::     |
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_wiring.png?nolink&0x200  }}
 +
 +<WRAP pagebreak></WRAP>
 +
 +===== Serial configuration and timeout =====
 +  * Available baudrates 2400, 9600, 19200, 38400 bps
 +  * Data bits and parity 8N1, 7E1, 8E1, 8N2
 +  * :!: Max 64 bytes per transmition
 +  * Integrated 240 Ohm termination resistor
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_serial.png?nolink&0x500  }}
 +
 +===== Wireless binding =====
 +
 +==== Create new secure group ====
 +  
 +  * turn on all devices at the same time
 +  * within 10 seconds, while RF LED is blinking, press and hold button on one of the devices
 +  * after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address.
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_configuration_1.png?nolink&0x500  }}
 +
 +==== Add new device to the group ====
 +  
 +  * turn on the device
 +  * within 10 seconds, press and hold button on one of the existing devices
 +  * after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent.
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_configuration_2.png?nolink&0x500  }}
 +
 +==== Topology examples ====
 +  
 +  * Modbus master, connected to 12 slaves using a pair of WM-1 devices
 +  * Modbus master, connected to 10 slaves, organized in two groups
 +  * Modbus master, connected to 5 slaves, each one having local WM-1 device
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_topology.png?nolink&0x500  }}
 +
 +==== Multiple groups ====
 +  
 +  * When the system has two or more separate Modbus lines, they should be configured as separate groups. 
 +  * Each group has a single master and one or more slaves.
 +  * Groups can't talk to each other, but they share the same bandwidth. 
 +  * Two masters may start transmitting at the same time causing collisions. 
 +  * To reduce number of missed messages, keep the traffic low.
 +  
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_multiplegroups.png?nolink&0x500  }}
 +
 +===== Connection check =====
 +  * Press button shortly
 +  * RF LED will blink shortly on each connected device
 +  * Serial interface is unaffected
 +
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_connectioncheck.png?nolink&0x150  }}
 +
 +===== Factory reset =====
 +  * Hold button and turn the device ON
 +  * RF led will blink twice. Group address is now reset to default. 
 +  * Other devices will not be affected.
 +
 +{{ wiki:20_rdc_charger:03_hardware:wm1_factoryreset.png?nolink&0x200  }}