-====== Wireless Modbus-to-Modbus bridge ====== 
  
-**Wireless Modbus-to-Modbus bridge** 
- 
-<WRAP column 350px> 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_module.png?nolink |}} 
- 
-</WRAP> 
- 
-<WRAP column 300px> 
- 
-| Model number: ^ WM-1       | 
-| Frequency:    | ISM 868MHz (EU) | 
-| Dimensions:   | 93x45x27 mm     | 
- 
-===== Applications ===== 
- 
-  * Replacement for RS485 wiring solution with wireless. Optimal for long range Modbus RTU serial communications with half duplex configuration. 
- 
-</WRAP> 
- 
-<WRAP clear></WRAP> 
- 
-===== Installation and mounting ===== 
-  * :!: Carefully open WM-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout) 
-  * :!: Place WM-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets. 
-  * Connect RS485 terminals to WM-1 RS485 terminals 
-    * A - A 
-    * B - B 
-    * C - GND 
-  * Connect to 230V power supply 
-  * Bind modules to wireless network 
- 
- 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_module_diagram.png?nolink&0x500  }} 
-{{ :wiki:rdx_charger:03_hardware:wm1_mounting.png?nolink&0x500  }} 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Features ===== 
- 
-  * replacement for RS485 wiring 
-  * Modbus RTU serial protocol 
-  * wired/wireless combinations 
-  * very long range, no hopping 
-  * protected private connection 
-  * multiple slaves per device 
-  * multiple addressable groups 
- 
- 
-===== Technical specification ===== 
- 
-| Power supply:          |                                230V, 50/60Hz, 1W | 
-| Ingress protection:    |                                    IP20 | 
-| Operating temperature: |                                 -20..50°C | 
-| Storage temperature:                                 -40..85°C | 
-| Relative humidity:                                  0..85% n/c | 
- 
-===== Terminals and wiring =====  
- 
-| To power sensor ^ A | RS485 bus  | 
-| :::            ^ B | :::        | 
-| :::            ^ C | :::        | 
-| To power supply ^ L| 230V AC | 
-| :::             ^ N| :::     | 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_wiring.png?nolink&0x200  }} 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Serial configuration and timeout ===== 
-  * Available baudrates 2400, 9600, 19200, 38400 bps 
-  * Data bits and parity 8N1, 7E1, 8E1, 8N2 
-  * :!: Max 64 bytes per transmition 
-  * Integrated 240 Ohm termination resistor 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_serial.png?nolink&0x500  }} 
- 
-===== Wireless binding ===== 
- 
-==== Create new secure group ==== 
-   
-  * turn on all devices at the same time 
-  * within 10 seconds, while RF LED is blinking, press and hold button on one of the devices 
-  * after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address. 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_configuration_1.png?nolink&0x500  }} 
- 
-==== Add new device to the group ==== 
-   
-  * turn on the device 
-  * within 10 seconds, press and hold button on one of the existing devices 
-  * after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent. 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_configuration_2.png?nolink&0x500  }} 
- 
-==== Topology examples ==== 
-   
-  * Modbus master, connected to 12 slaves using a pair of WM-1 devices 
-  * Modbus master, connected to 10 slaves, organized in two groups 
-  * Modbus master, connected to 5 slaves, each one having local WM-1 device 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_topology.png?nolink&0x500  }} 
- 
-==== Multiple groups ==== 
-   
-  * When the system has two or more separate Modbus lines, they should be configured as separate groups.  
-  * Each group has a single master and one or more slaves. 
-  * Groups can't talk to each other, but they share the same bandwidth.  
-  * Two masters may start transmitting at the same time causing collisions.  
-  * To reduce number of missed messages, keep the traffic low. 
-   
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_multiplegroups.png?nolink&0x500  }} 
- 
-===== Connection check ===== 
-  * Press button shortly 
-  * RF LED will blink shortly on each connected device 
-  * Serial interface is unaffected 
- 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_connectioncheck.png?nolink&0x150  }} 
- 
-===== Factory reset ===== 
-  * Hold button and turn the device ON 
-  * RF led will blink twice. Group address is now reset to default.  
-  * Other devices will not be affected. 
- 
-{{ :wiki:rdx_charger:03_hardware:wm1_factoryreset.png?nolink&0x200  }} 